It is advisable to have sprinkler
systems inspected regularly by a
qualified inspection service. Length of
time between such inspections can
vary due to accessibility, ambient
atmosphere, water supply, and site
activity.
Do not attempt to re-assemble or
otherwise reuse a sprinkler that has
operated. Replace any sprinkler
exhibiting corrosion or damage; always
use new sprinklers of the same type
and temperature rating as replacements.
Because the discharge pattern is
critical to protection of life and property,
nothing should be hung or attached to
the sprinkler unit that would disrupt the
discharge pattern. Such obstructions
must be removed. In the event that
construction has altered the original
configuration, additional sprinklers may
need to be installed to maintain the
protection level.
Do not attempt to replace sprinklers
without first removing the fire protection
system from service. Be certain to
secure permission from all
Authorities
Having Jurisdiction, and notify all
personnel who may be affected during
system shutdown. A fire watch during
maintenance periods is a
recommended precaution.
To remove the system from service
mode, first refer to the system
operating guide and valve instructions.
Drain water and relieve pressure in the
pipes. Remove the existing unit and
install the replacement, using only the
special sprinkler wrench. Be certain to
match model, style, orifice, and
temperature rating.
A fire protection system that has
been shut off after activation should be
returned to service immediately.
Inspect the entire system for damage
and replace or repair as necessary.
HEC-12EC PRO.1
Central Sprinkler Company
451 N. Cannon Avenue, Lansdale, PA 19446
Phone (215) 362-0700
FAX (215) 362-5385
Sprinklers that did not operate but were
subjected to corrosive elements of
combustion or excessive temperatures
should be inspected, and replaced if
need be. The
Authority Having Jurisdic-
tion will detail minimum replacement
requirements and regulations.
Guarantee: Central Sprinkler
Company will repair and/or replace any
product found to be defective in material
or workmanship within a period of one
year from date of shipment. Please refer
to the current Price List for further
details of the warranty.
(and closure plate) up tight against the
mounting surface. The tamper resistant
retaining screws can only be installed or
removed using the special tamper-proof
socket.
Caution: Special care must be taken
when installing with a CPVC system.
Sprinklers must be installed after the
manufacturer's recommended setting
time for the primer and cement to
ensure that neither accumulate within
the sprinkler.
Special care must be taken when
installing with a copper system.
Sprinklers must be installed only after
the inside of the sprinkler nipple and
associated fittings have been wire
brushed to remove any flux. Residual
flux can cause corrosion and in
extreme cases can impair proper
sprinkler operation.
Sprinklers must be handled carefully.
They must not be transported or stored
where ambient temperatures may
exceed 100
o
F/38
o
C. For best results,
store them in a cool, dry location in the
original shipping package.
Do not install sprinklers that have
been dropped or visibly damaged.
Sprinklers must never be painted,
coated, plated, or altered in any other
way from manufactured condition or
they may not function properly. Any
sprinklers altered in such a manner
must be replaced.
The owner is responsible for the
proper working condition of all fire
protection devices and accessories.
The NFPA Standard 25 entitled,
“Inspection, Testing and Maintenance
of Water-Based Fire Protection
Systems”, contains guidelines and
minimum maintenance requirements.
Furthermore, the local
Authority Having
Jurisdiction may have additional
regulations and requirements for
maintenance, testing, and inspection
that must be obeyed.
Care &
Maintenance
Ordering Information: When placing
an order, indicate the full product name.
Please specify the quantity, model,
style, orifice size, temperature rating,
sprinkler finish, escutcheon finish,
closure plate(s) and finish, sprinkler
wrench and special tamper-proof socket.
For special painted escutcheon
finishes, the customer must provide
quick-dry paint preferably in a lacquer
base to ensure proper color duplication.
Without which Central Sprinkler
Company cannot be responsible for
acceptable color matching.
Availability and Service: Central
sprinklers, accessories, and other
products are available throughout the
U.S. and Canada, and internationally,
through a network of Central Sprinkler
Company distribution centers. You may
write directly to Central Sprinkler
Company or call (215) 362-0700 for the
distributor nearest you.
Patents: The Omega Prohibitor
TM
Automatic Sprinklers are protected
under U.S. Patent No. 4,491,182.
Additional patents are pending.
Conversion Table:
1 inch = 25.400 mm
1 foot = 0.3048 M
1 pound = 0.4536 kg
1 foot pound = 1.36 Nm
1 psi = 6.895 Kpa
= 0.0689 bar
= 0.0703 kg/cm
2
1 U.S. gallon = 3.785 dm
3
= 3.785 liters
Conversions are approximate.