Technical
Data

Design Requirements —  Extended Coverage Quick Response Applications

Design
Data

*Teflon is a trademark of the DuPont Corp.

Coverage Area

Minimum

"A"

Width

Throw

Flow

Deflector Distance

Temperature

(Ft.)

(Ft.)

(pressure)

Below Ceiling

Rating

16

18

29 gpm (26.8 psi)

4" - 6"

160

o

F/71

o

C

16

18

30 gpm (28.7 psi)

6" - 12"

160

o

F/71

o

C

16

20

32 gpm (32.7 psi)

4" - 6"

160

o

F/71

o

C

         Coverage Area

Minimum

"A"

Width

Throw

Flow

Deflector Distance

Temperature

(Ft.)

(Ft.)

(pressure)

Below Ceiling

Rating

16

16

26 gpm (21.6 psi)

4" - 12"

 145

o

F/63

o

C;160

o

F/71

o

C

16

18

29 gpm (26.8 psi)

4" - 6"

145

o

F/63

o

C

16

18

30 gpm (28.7 psi)

6" - 12"

145

o

F/63

o

In Extended Coverage Quick Response Applications, the Model HEC-12EC PRO
Sprinklers are listed for installation in light hazard occupancies  only.

Installation Sequence

Step 1.  The sprinkler must be
installed in the horizontal position 4"
to 12" below ceiling.

Step 2.   Install the steel nipple into
the branch line fitting, then slide the
rigid support collar over the nipple
prior to installing the 1" x 

1

2

" reducing

coupling.  The face of the sprinkler
fitting should be installed:

(a)  1

7

16

" (

±

1

16

") behind the finished

wall if no closure plate is
utilized.

(b)  1

3

8

" (

±

1

16

") behind the finished

wall if the light gauge
escutcheon closure plate is
utilized.

(c)  1

5

16

" (

±

1

16

") behind the finished

wall if the security    

 closure

plate is utilized.

   The sprinkler nipple must be fitted
with the rigid support collar to prevent
movement of the sprinkler away from
the finished wall surface (see
installation diagram on page 2).

Step 3.  Use only a non-hardening
pipe joint compound or Teflon* tape.
Apply to the male threads only.

Model:  HEC-12EC PRO
Style:  Horizontal Sidewall
Orifice Size:  

1

2

(12.7 mm)

K Factor:  5.6 

(80.08)

Thread Size:  

1

2

(12.7 mm)

 N.P.T.

Temperature Rating:

145

°

F/63

°

C,

160

o

F/71

o

C

Approvals:  U.L., U.L.C.,

M.E.A. (46-92-M Vol. II)

Maximum Working Pressure:  175 psi
Factory Hydro Test:  100% at 500 psi
Standard Finishes:

Sprinkler:  brass, chrome plated
Escutcheon: brass, chrome plated,
                     white painted

Escutcheon Closure Plate:  brass,

chrome plated, white painted

Security Closure Plate:  chrome

plated, brass plated,
white painted

Length:  2

3

8

(60.3 mm)

Width:    2" 

(50.8 mm)

Weight:  6.8 oz. 

(193 grams)

Prohibitor

TM

 sprinklers must be

installed in accordance with current
NFPA 13.  Deviations from these
requirements and standards, or any
alteration to the sprinkler itself, will
void any warranty made by Central
Sprinkler Company.  In addition,
installation must also meet local
government provisions, codes, and
standards as applicable.

The system piping must be properly

sized to ensure the proper flow rate at
the sprinkler.

Prior to installation, check for

proper model, style, orifice size, and
temperature rating. Install sprinklers
after the piping is in place to avoid
mechanical damage; replace any
damaged unit. Wet pipe systems
must be protected from freezing.

Upon completion of the installation,

the system must be tested per
recognized standards.

In the event of a thread leak,

remove the unit, apply new pipe joint
compound or tape, and reinstall.

Design Requirements — Extended Coverage Applications

Installation

Step 4.  Hand tighten the sprinkler into
the reducing coupling.  Use an Omega
HEC sprinkler wrench to tighten the
unit into the fitting.  A leak tight joint
requires the application of only 7 to 14
ft.-lbs. of torque. A tangential force of
14 to 28 lbs. delivered through a 6"
long handle will deliver adequate
torque.  Torque levels over 21 ft.-lbs
may distort the orifice seal, resulting in
leakage.

Step 5.  During installation of the
sprinkler, check the alignment of
retaining collar holes with final
orientation of sprinkler escutcheon.

Step 6.  To install the escutcheon plate
(and closure plate if applicable),
align it (them) with and press it (them)
over the sprinkler body until the outer
edge of the escutcheon (or closure
plate) meets the  mounting surface.  Do
not over or under tighten the sprinkler
to compensate for inaccurate
escutcheon plate adjustment.

Step 7.  Install the tamper resistant
retaining screws through the
escutcheon and into the retaining
collar, thereby drawing the escutcheon

In Extended Coverage Applications, the Model HEC-12EC PRO Sprinklers are listed for
installation in light hazard occupancies  only.

OBSOLETE

Содержание CENTRAL Omega HEC-12EC PRO

Страница 1: ...r pressure to force the orifice sealing mechanism and deflector assembly open Water is then discharged in a designed flow pattern The Omega ProhibitorTM Model HEC 12EC PRO Automatic Sprinklers have been specifically designed for use in institutional occupancies such as correctional facilities and mental health facilities where the occupants may attempt to tamper with or otherwise employ the sprink...

Страница 2: ...w 1 2 1 4 1 16 3 4 2 3 4 3 8 A 2 1 4 Dia Hole in Wall 2 1 2 Escutcheon 4 1 2 Dia Security Closure Plate 3 5 8 Dia Escutcheon Closure Plate 1 7 16 1 16 No Closure Plate 1 3 8 1 16 Escutcheon Closure Plate 1 5 16 1 16 Security Closure Plate Note The special tamper proof socket must be used for installation or removal of the tamper resistant retaining screws Rigid Support Collar with Bolt Part 162 01...

Страница 3: ...brass chrome plated white painted Security Closure Plate chrome plated brass plated white painted Length 23 8 60 3 mm Width 2 50 8 mm Weight 6 8 oz 193 grams ProhibitorTM sprinklers must be installed in accordance with current NFPA 13 Deviations from these requirements and standards or any alteration to the sprinkler itself will void any warranty made by Central Sprinkler Company In addition insta...

Страница 4: ...ket Caution Special care must be taken when installing with a CPVC system Sprinklers must be installed after the manufacturer s recommended setting time for the primer and cement to ensure that neither accumulate within the sprinkler Special care must be taken when installing with a copper system Sprinklers must be installed only after the inside of the sprinkler nipple and associated fittings hav...

Отзывы: