©1998 Central Sprinkler Company
Printed in U.S.A.
maintain the protection level.
Do not attempt to replace sprinklers
without first removing the fire
protection system from service. Be
certain to secure permission from all
Authorities Having Jurisdiction, and
notify all personnel who may be
affected during system shutdown. A
fire watch during maintenance periods
is a recommended precaution.
To remove the system from
service mode, first refer to the system
operating guide and valve instruction.
Drain water and relieve pressure in
the pipes. Remove the existing unit
and install the replacement, using
only the special sprinkler wrench. Be
certain to match model, style, orifice,
and temperature rating.
A fire protection system that has
been shut off after an activation
should be returned to service
immediately. Inspect the entire
system for damage and replace or
repair as necessary. Sprinklers that
did not operate, but were subjected to
corrosive elements of combustion or
excessive temperatures should be
inspected and replaced if needed.
The
Authority Having Jurisdiction will
detail minimum replacement
requirements and regulations.
Guarantee: Central Sprinkler
Company will repair and/or replace
any products found to be defective in
material or workmanship within a
period of one year from the date of
shipment. Please refer to the current
Price List for further details of the
warranty.
Ordering
Information
Ordering Information: When
placing an order, indicate the full
product name. Please specify the
quantity, model, style, orifice size,
temperature rating, type of finish and
sprinkler wrench.
Availability and Service: Central
sprinklers, valves, accessories, and
other products are available
throughout the U.S. and Canada; and
internationally through a network of
Central Sprinkler distribution centers.
You may write directly to Central
Sprinkler Company or call (215) 362-
0700 for the distributor nearest you.
Patents: Patents are pending.
Conversion Table:
1 inch = 25.400 mm
1 foot = 0.3048 m
1 pound = 0.4536 kg
1 foot pound = 1.36 Nm
1 psi = 6.895 kpa
= 0.0689 bar
= 0.0703 kg/cm2
1 U.S. gallon = 3.785 dm3
= 3.785 liters
Conversions are approximate.
shipping package.
Do not install sprinklers that have
been dropped or visibly damaged.
Sprinklers must never be painted,
coated, plated or altered in any other
way from manufactured condition or
they may not function properly. Any
sprinklers altered in such manner
must be replaced.
The owner is responsible for the
proper operating condition of all fire
protection devices and accessories.
The NFPA Standard 25 entitled,
“Inspection, Testing and Maintenance
of Water-Based Fire Protection
Systems”, contains guidelines and
minimum maintenance requirements.
Furthermore, the local
Authority
Having Jurisdiction may have
additional regulations and
requirements for maintenance,
testing, and inspection that must be
obeyed.
It is recommended that sprinkler
systems be inspected regularly by a
qualified inspection service. Length of
time between such inspections can
vary due to accessibility, ambient
atmosphere, water supply and site
activity.
Do not attempt to reassemble or
otherwise reuse a sprinkler that has
operated. Replace any sprinkler
exhibiting corrosion or damage.
Always use new sprinklers of the
same type and temperature rating as
replacements.
Because the discharge pattern is
critical to protection of life and
property, nothing should be hung or
attached to the sprinkler unit that
would disrupt the pattern. Such
obstructions must be removed. In the
event that construction has altered
the original configuration, additional
sprinklers should be installed to
H
17
⁄
32
.2
Central Sprinkler Company
451 N. Cannon Avenue, Lansdale, PA 19446
Phone (215) 362-0700
FAX (215) 362-5385