Installation

The Model ESFR-25 Pendent Sprin-
klers are to be installed in accordance
with the following instructions:

NOTE

Damage to the fusible Link Assembly
during installation can be avoided by
handling the  sprinkler by  the  frame
arms only (i.e., do not apply pressure
to the fusible Link Assembly), and by
using

the

appropriate

sprinkler

wrench. Damaged sprinklers must be
replaced.

A leak tight 1 inch NPT sprinkler joint
should be obtained with a torque of 20
to 30 ft.lbs. (26,8 to 40,2 Nm). Higher
levels of torque may distort the sprin-
kler inlet with consequent leakage or
impairment of the sprinkler.

Step 1.

The ESFR-25 Sprinkler must

be installed in the pendent position.

Step 2.

With pipe thread sealant ap-

plied, hand tighten the sprinkler into
the sprinkler fitting. Do not apply pres-
sure to the Link Assembly, and handle
the ESFR-25 Sprinkler only by the
Frame arms.

Step 3.

Wrench tighten the ESFR-25

Sprinkler using only the W-Type 1
Sprinkler Wrench (Ref. Figure 2) and
by fully engaging (seating) the wrench
on the sprinkler wrench flats.

Step 4.

After installation, inspect the

Link Assembly of each ESFR-25
Sprinkler for damage. In particular,
verify that the Link Assembly and Hook
are positioned as illustrated in Figure
1, and that the Link Assembly has not
been bent, creased, or forced out of its
normal position in any way.

Damaged sprinklers must be replaced.

Care and
Maintenance

The Model ESFR-25 must be main-
tained and serviced in accordance
with the following instructions:

NOTE

Before closing a fire protection system
main control valve for maintenance
work on the fire protection system that
it controls, permission to shut down the
affected fire protection systems must
be obtained from the proper authori-
ties and all personnel who may be
affected by this action must be notified.

Sprinklers that are found to be leaking
or exhibiting visible signs of corrosion
must be replaced.

Automatic sprinklers must  never be
shipped or stored where their tempera-
ture will exceed 100°F/38°C and they
must never be painted, plated, coated,
or otherwise altered after leaving the
factory. Modified or over-heated sprin-
klers must be replaced.

Care must be exercised to avoid dam-
age - before, during, and after instal-
lation. Sprinklers damaged  by drop-
ping,  striking, wrench twist/slippage,
or the like, must be replaced.

The owner is responsible for the in-
spection, testing, and maintenance of
their fire protection system and de-
vices in  compliance with this  docu-
ment, as well as with the applicable
standards of the National Fire Protec-
tion Association (e.g., NFPA 25), in
addition to the standards of any other
authorities having jurisdiction. The in-
stalling contractor or sprinkler manu-
facturer should be contacted relative to
any questions.

It is recommended that automatic
spr inkler systems be inspected,
tested, and maintained by a qualified
Inspection Service.

Limited
Warranty

Products manufactured by Tyco Fire
Products are warranted solely to the
original Buyer for ten (10) years
against defects in material and work-
manship when paid for and properly
installed and maintained under normal
use and service. This warranty will ex-
pire ten (10) years from date of ship-
ment by Tyco Fire Products. No war-
ranty

is

given

for

products

or

components manufactured by compa-
nies not affiliated by ownership with
Tyco Fire Products or for products and
components which have been subject
to misuse, improper installation, corro-
sion, or which have not been installed,
maintained, modified or repaired in ac-
cordance with applicable Standards of
the National Fire Protection Associa-
tion, and/or the standards of any other
Authorities Having Jurisdiction. Mate-
rials found by Tyco Fire Products to be
defective shall be either repaired or
replaced, at Tyco Fire Products’ sole
option. Tyco Fire Products neither as-
sumes, nor authorizes any person to
assume for it, any other obligation in
connection with the sale of products or
parts of products. Tyco Fire Products
shall not be responsible for sprinkler
system design errors or inaccurate or
incomplete information supplied by
Buyer or Buyer’s representatives.

IN NO EVENT SHALL TYCO FIRE
PRODUCTS BE LIABLE, IN CON-
TRACT, TORT, STRICT LIABILITY OR
UNDER ANY OTHER LEGAL THE-
ORY, FOR INCIDENTAL, INDIRECT,
SPECIAL OR CONSEQUENTIAL
DAMAGES, INCLUDING BUT NOT
LIMITED TO LABOR CHARGES, RE-
GARDLESS OF WHETHER TYCO
FIRE PRODUCTS WAS INFORMED
ABOUT THE POSSIBILITY OF SUCH
DAMAGES, AND IN NO EVENT
SHALL TYCO FIRE PRODUCTS’ LI-
ABILITY EXCEED   AN   AMOUNT
EQUAL TO THE SALES PRICE.

THE FOREGOING WARRANTY IS
MADE IN LIEU OF ANY AND ALL
OTHER WARRANTIES EXPRESS OR
IMPLIED, INCLUDING WARRANTIES
OF MERCHANTABILITY AND FIT-
NESS FOR A PARTICULAR PUR-
POSE.

TFP312