background image

Technical
Data

Approvals

UL and C-UL Listed. FM Approved.
(Refer to the Design Criteria Section.)
NYC under MEA 356-01-E

Maximum Working Pressure

175 psi (12,1 bar)

Pipe Thread Connection

1 inch NPT or ISO 7-R1

Discharge Coefficient

K = 25.2 GPM/psi

1/2

(362,9 LPM/bar

1/2

)

Temperature Ratings

165°F/74°C or 214°F/101°C

Finish

Natural Brass

Physical Characteristics

Frame . . . . . . . . . . . . . . Brass
Deflector . . . . . . . . . . . Bronze
Compression Screw . . . . . . . . .

. . . . . . . . . . . . Stainless Steel

Hook

. . . . . . . . . . . . . . Monel

Strut

. . . . . . . . . . . . . . Monel

Link Assembly . . . . Solder, Nickel
Button . . . . . . . . . . . . . . Brass
Sealing Assembly . . . . . . . . . .

. . . . .

Beryllium Nickel w/Teflon*

Ejection Spring . . . . . . . . Inconel

Patents

U.S.A.

Patent

Numbers 4,580,729

5,829,532, and 6,059,044 may be ap-
plicable to the Model ESFR-25. Other
patents are pending.

Operation

The fusible link assembly is comprised
of two link halves which are joined
together by a thin layer of solder. When
the rated temperature is reached, the
solder melts and the two link halves
separate activating the sprinkler and
flowing water.

Design
Criteria

UL AND C-UL LISTING CRITERIA

The Model ESFR-25 (SIN TY9226)
Sprinklers are UL and C-UL Listed as
“Early Suppression Fast Response
Sprinklers” for installation per NFPA 13
or other applicable NFPA standards.

UL AND C-UL SPECIFIC
APPLICATION LISTING CRITERIA

The Model ESFR-25 (SIN TY9226)
Sprinklers are UL and C-UL Listed as
“Specific Application Early Suppres-
sion Fast Response Sprinklers” for use
in in accordance with NFPA 13 to pro-
tect single-, double-, and multiple row
rack storage and palletized and solid
pile storage (no open  containers or
solid shelves) of Class I, II, III, and IV
commodities encapsulated or unen-
capsulated and cartoned Group A un-
expanded plastics when installed with

the following storage and ceiling
heights and minimum design pres-
sures:

Maximum Maximum

Minimum

Storage

Ceiling

Flowing

Height,

Height,

Pressure,

Ft. (m)

Ft. (m)

psi (bar)

40 (12,2)

45 (13,7)

40 (2,7)

35 (10,7)

40 (12,2)

25 (1,7)

30 (9,1)

35 (10,7)

20 (1,4)

25 (7,6)

30 (9,1)

15 (1,0)

When applying the specific application
listing criteria, the Model ESFR-25
Sprinklers should  be installed  using
the same installation obstruction and
construction criteria, as well as deflec-
tor-to ceiling distances, as is applica-
ble for Early Suppression  Fast Re-
sponse Sprinklers having a nominal
K-Factor of 25.2 per NFPA 13.

FM APPROVAL CRITERIA

The Model ESFR-25 (SIN TY9226)
Sprinklers are FM Approved as “Early
Suppression Fast Response Sprin-
klers” for installation per the applicable
FM Loss Prevention Data Sheets.

Page 2 of 4

TFP312

1-Frame
2-Deflector
3-Compression Screw
4-Hook
5-Strut
6-Link Assembly
7-Button
8-Sealing Assembly
9-Ejection Spring

FIGURE 1, MODEL ESFR-25 EARLY SUPPRESSION FAST RESPONSE PENDENT SPRINKLER