©1998 Central Sprinkler Company
   Printed in U.S.A.

ELO-16 GB FR OH.1

Ordering
Information

Ordering Information: When placing an
order, indicate the full product name.
Please specify the quantity, model, style,
orifice size, temperature rating, type of
finish or coating, and sprinkler wrench.

Availability and Service: Central
sprinklers, valves, accessories, and
other products are available throughout
the U.S. and Canada, and internation-
ally, through a network of Central
Sprinkler distribution centers. You may
write directly to Central Sprinkler Com-
pany, or call (215) 362-0700 for the
distributor nearest you.

Guarantee: Central Sprinkler Company
will repair and/or replace any products
found to be defective in material or
workmanship within a period of one year
from the date of shipment. Please refer
to the current Price List for further details
of the warranty.

Patents:  The ELO-16 GB FR Optima™
sprinklers are protected under U.S.
Patent No. 5,366,022.

Conversion Table:
1 inch = 25.400 mm
1 foot = 0.3048 m
1 pound = 0.4536 kg
1 foot pound = 1.36 Nm
1 psi = 6.895 kpa
         = 0.0689 bar

  = 0.0703 kg/cm

2

1 U.S. gallon = 3.785 dm

3

  = 3.785 liters

Conversions are approximate.

OPTIMA™ is a registered trademark of
Central Sprinkler Company.

Sprinklers must be handled care-

fully. They must not be transported or
stored where ambient temperature
may exceed 100

°

F/38

°

C. For best

results, store them in a dry, cool
location in the original shipping
package.

Do not install sprinklers that have

been dropped or visibly damaged.
Sprinklers should never be painted,
coated, plated, or altered in any other
way from manufactured condition or
they may not function properly. Any
sprinklers altered in such manner
must be replaced.

The owner is responsible for the

proper operating condition of all fire
protection devices and accessories.
The NFPA Standard 25 entitled,
“Inspection, Testing and Maintenance
of Water-Based Fire Protection
System”, contains guidelines and
minimum maintenance requirements.
Furthermore, the local 

Authority

Having Jurisdiction may have addi-
tional regulations and requirements

for maintenance, testing, and inspec-
tion that must be obeyed.

It is advisable to have sprinkler

systems inspected regularly by a
qualified inspection service.  Length
of time between such inspections can
vary due to accessibility, ambient
atmosphere, water supply, and site
activity.

Do not attempt to reassembly or

otherwise reuse a sprinkler that has
operated.  Replace any sprinkler
exhibiting corrosion or damage;
always use new sprinklers of the
same type and temperature rating as
replacements.

Because the discharge pattern is

critical to protection of life and
property, nothing should be hung or
attached to the sprinkler unit that
would disrupt the pattern.  Such
obstructions must be removed.  In the
event that construction has altered
the original configuration, additional
sprinklers should be installed to
maintain the protection level.

Do not attempt to replace sprinklers

without first removing the fire protec-
tion system from service.  Be certain
to secure permission from all 

Authori-

ties Having Jurisdiction, and notify all
personnel who may be affected
during system shutdown.  A fire
watch during maintenance periods is
a wise precaution.

To remove the system from service

mode, first refer to the system
operating guide and valve instruction.
Drain the water and relieve pressure
in the pipes.  Remove the existing
unit and install the replacement, using
only the special sprinkler wrench.  Be
certain to match the model, style,
orifice, and temperature rating.

A fire protection system that has

been shut off after an activation
should be returned to service immedi-

Installation Sequence

Step 1.  For Recessed Pendent
Sprinklers, the face of the sprinkler
fitting should be installed a nominal 

3

4

"

(

±

3

8

")/ 19.1mm (

±

9.5mm) behind the

ceiling line.  Adjustments are made via
the push-on escutcheon.

Step 2.  Use only a non-hardening
pipe joint compound or Teflon* tape.
Apply only to the male threads.

Step 3.  Hand tighten the sprinkler into
the fitting.  Use the appropriate Central
wrench to tighten the unit into the
fitting.  A leak-tight joint requires only 7
to 14 ft.-lbs.( 9.5 to 19.0 Nm) of torque;
a tangential force of 14 to 28 lbs. (62.3
to 124.5 N) delivered through a 6" (150
mm) handle will deliver adequate
torque.  Torque levels over 21 ft.-lbs.
(28.6 Nm) may distort the orifice seal,
resulting in leakage.
   The upright sprinklers shall be
oriented so the frame arms are parallel
with the branch line pipe per NFPA.

ately.  Inspect the entire system for
damage and replace or repair as
necessary.  Sprinklers that did not
operate but were subjected to corro-
sive elements of combustion or
excessive temperatures should be
inspected, and replaced if need be.
The 

Authority Having Jurisdiction will

detail minimum replacement require-
ments and regulations.

*Teflon is a trademark of the DuPont Corp.

Care &
Maintenance

Central Sprinkler Company