2

ELO-16 GB FR Extended Coverage

Ordinary Hazard Upright

ELO-16 GB FR

Extended Coverage Ordinary Hazard Recessed Pendent

Installation

All Central Model ELO-16 GB FR

Automatic Glass Bulb Sprinklers must
be installed according to current NFPA
13 Standards and these installation
instructions.  Deviations from these
requirements and standards or any
alteration to the sprinkler itself will void
any warranty made by Central Sprinkler
Company.  In addition, installation must
also meet local government provisions,
codes, and standards as applicable.

The system piping must be properly

sized to ensure the minimum required
flow rate at the sprinkler.  Check for the
proper model, style, orifice size, and
temperature rating prior to installation.
Install sprinklers after the piping is in
place to avoid mechanical damage;
replace any damaged units.

 Upon completion of the installation,

the system must be tested per
recognized standards.

In the event of a thread leak, remove

the unit, apply new pipe joint compound
or tape, and reinstall.

Note:  Central's Model 65 or 401 escutcheon may be used.  When using

Central's Model 65 escutcheon, the face of R.C. is to protrude 1/8"

±

1/16" (3.2mm 

±

1.6mm) beyond the finished ceiling line.

Face of

Reducing

Coupling

Finished

Ceiling LIne

1" x 3/4" (25 x20mm)

Reducing Coupling

ELO  .64

Model ELO (2-piece)

Recessed Escutcheon

3/8" (9.5mm) Min.

1 1/8" (28.6mm) Max.

2 1/4" Dia. Min. (57.2mm)

2 3/4" Dia. Max. (69.9mm)

3 1/4" Diameter

(82.6mm)

1/8"

1" x 3/4"

(25x20 mm)

Reducing Coupling

ELO  .64

3 1/8"

(79.4mm)

1 7/8" (47.6mm)

Diamater

2 3/8"

(60.3 mm)

(Ref.)

ELO-16 GB FR Extended Coverage

Ordinary Hazard Pendent

3 1/8"

(79.4mm)

ELO   .64

2" Diameter

(50.8mm)