ELO-16 GB FR Extended Coverage
Ordinary Hazard Upright
ELO-16 GB FR
Extended Coverage Ordinary Hazard Recessed Pendent
Installation
All Central Model ELO-16 GB FR
Automatic Glass Bulb Sprinklers must
be installed according to current NFPA
13 Standards and these installation
instructions. Deviations from these
requirements and standards or any
alteration to the sprinkler itself will void
any warranty made by Central Sprinkler
Company. In addition, installation must
also meet local government provisions,
codes, and standards as applicable.
The system piping must be properly
sized to ensure the minimum required
flow rate at the sprinkler. Check for the
proper model, style, orifice size, and
temperature rating prior to installation.
Install sprinklers after the piping is in
place to avoid mechanical damage;
replace any damaged units.
Upon completion of the installation,
the system must be tested per
recognized standards.
In the event of a thread leak, remove
the unit, apply new pipe joint compound
or tape, and reinstall.
Note: Central's Model 65 or 401 escutcheon may be used. When using
Central's Model 65 escutcheon, the face of R.C. is to protrude 1/8"
±
1/16" (3.2mm
±
1.6mm) beyond the finished ceiling line.
Face of
Reducing
Coupling
Finished
Ceiling LIne
1" x 3/4" (25 x20mm)
Reducing Coupling
ELO .64
Model ELO (2-piece)
Recessed Escutcheon
3/8" (9.5mm) Min.
1 1/8" (28.6mm) Max.
2 1/4" Dia. Min. (57.2mm)
2 3/4" Dia. Max. (69.9mm)
3 1/4" Diameter
(82.6mm)
1/8"
1" x 3/4"
(25x20 mm)
Reducing Coupling
ELO .64
3 1/8"
(79.4mm)
1 7/8" (47.6mm)
Diamater
2 3/8"
(60.3 mm)
(Ref.)
ELO-16 GB FR Extended Coverage
Ordinary Hazard Pendent
3 1/8"
(79.4mm)
ELO .64
2" Diameter
(50.8mm)