Design
Data

Caution:  Minimum spacing between  sprinklers is 12' (3.7m) for

upright and 12'-6" (3.81m) for pendent.

Design Requirements — Commercial Extended Coverage Applications

Ordinary Hazard, Group 3, Density 0.21 GPM/ft

2

 - NFPA 13 1989 or earlier

Minimum Distance From Deflector to Top of Commodities is 18".

Design Requirements — Commercial Extended Coverage Applications

Ordinary Hazard, Group 2, Density 0.20 GPM/ft

2

 - NFPA 13 1991 and later

Minimum Distance From Deflector to Top of Commodities is 18".

Design Requirements — Commercial Extended Coverage Applications

Ordinary Hazard, Group 2, Density 0.19 GPM/ft

2

 - NFPA 13 1989 or earlier

Minimum Distance From Deflector to Top of Commodities is 18".

Maximum

Minimum Design

Minimum Design

Spacing Between

Location From

Flow per Sprinkler

Pressure per Sprinkler

Sprinklers

Any Wall

GPM

(Lpm)

PSI

(bar)

14 x 14 feet (196 sq. ft.) 

/4.3m x 4.3m (18.2m

2

)

7 feet 

(2.1m)

31.4 

(111.4)

7.6 

(0.5)

16 x 16 feet (256 sq. ft.) 

/4.9m x 4.9m (23.8m

2

)

8 feet 

(2.4m)

41.0 

(145.5)

12.9 

(0.9)

Design Requirements — Commercial Extended Coverage Applications

Ordinary Hazard, Group 1, Density 0.16 GPM/ft

2

 - NFPA 13 1989 or earlier

Minimum Distance From Deflector to Top of Commodities is 18".

Design Requirements — Commercial Extended Coverage Applications

Ordinary Hazard, Group 1, Density 0.15 GPM/ft

2

 - NFPA 13 1991 and later

Minimum Distance From Deflector to Top of Commodities is 18".

Maximum

Minimum Design

Minimum Design

Spacing Between

Location From

Flow per Sprinkler

Pressure per Sprinkler

Sprinklers

Any Wall

GPM

(Lpm)

PSI

(bar)

14 x 14 feet (196 sq. ft.)/

4.3m x 4.3m (18.2m

2

)      7 feet (2.1m)

 30.2 

(114.5)

7.0 

(0.5)

16 x 16 feet (256 sq. ft.)/

4.9m x 4.9m (23.8m

2

)      8 feet (2.4m)

 38.4 

(145.5)

11.3 

(0.8)

For FM Projects

Consult the Factory Mutual Guidelines for

specific Factory Mutual requirements if Factory

Mutual Approval is required.

Maximum

Minimum Design

Minimum Design

Spacing Between

Location From

Flow per Sprinkler

Pressure per Sprinkler

Sprinklers

Any Wall

GPM

(Lpm)

PSI

(bar)

14 x 14 feet (196 sq. ft.) 

/4.3m x 4.3m (18.2m

2

)

7 feet 

(2.1m)

37.2 

(141.0)

10.6 

(0.7)

16 x 16 feet (256 sq. ft.) 

/4.9m x 4.9m (23.8m

2

)

8 feet 

(2.4m)

48.6 

(184.2)

18.2 

(1.3)

Maximum

Minimum Design

Minimum Design

Spacing Between

Location From

Flow per Sprinkler

Pressure per Sprinkler

Sprinklers

Any Wall

GPM

(Lpm)

PSI

(bar)

14 x 14 feet (196 sq. ft.) 

/4.3m x 4.3m (18.2m

2

)

7 feet 

(2.1m)

39.2 

(148.6)

11.8 

(0.8)

16 x 16 feet (256 sq. ft.) 

/4.9m x 4.9m (23.8m

2

)

8 feet 

(2.4m)

51.2 

(194.0)

20.2 

(1.4)

Maximum

Minimum Design

Minimum Design

Spacing Between

Location From

Flow per Sprinkler

Pressure per Sprinkler

Sprinklers

Any Wall

GPM

(Lpm)

PSI

(bar)

14 x 14 feet (196 sq. ft.) 

/4.3m x 4.3m (18.2m

2

)

7 feet 

(2.1m)

41.2 

(156.1)

13.1 

(0.9)

16 x 16 feet (256 sq. ft.) 

/4.9m x 4.9m (23.8m

2

)

8 feet 

(2.4m)

53.8 

(203.9)

22.3 

(1.5)