Pendents Located Along Multiple Slopes

• Spacing is measured along the slope.

• One row of sprinklers is shown on the sloping ceiling for

clarity. Actual number of sprinklers within a compartment  is
unlimited.

• Cathedral ceiling applications:  An 8" minimum beam or

lintel is required at the peak.

• If a loft adjoins the sloped ceiling compartment, a

minimum 8" deep lintel is required between the loft and
the ceiling.

• Hydraulic calculations shall conform to the appropriate

NFPA standard.  Calculate the two (NFPA 13D) or four
(NFPA 13R) most demanding sprinklers along one slope.
If there are less than two (NFPA 13D) or four (NFPA 13R)
sprinklers along one slope, calculate all the sprinklers
along one slope.  For ceilings with adjoining lofts, add one
sprinkler in the loft to the hydraulic calculations.

• Openings in the perimeter walls, such as a doorway or

adjoining hallway, must maintain a maximum height of 8 feet
or less.

Figure  4 - UL Specific Application Sloped Ceiling Design Criteria

a

a

b

b

D = MAXIMUM SLOPE

8:12 (33.7

O

)

D

a

a

Figure  5 - Sprinkler Location for Sloped Ceiling

Note the minimum distance between sprinklers changes by
the angle of the slope.  Verify the Listed flows and pressures
for “maximum” and “1/2  maximum” distances.   Dimensions
“A” and “B” are measured along the slope.  For angles
greater than 60

°

, verify with Central's Technical Services

Department.

A — NFPA minimum of 4" (verify “G” dimension minimum of

4"), maximum 1/2 of the Listed spacing that the sprinkler
was calculated for.  (i.e., 18' x 18' spacing is maximum of
9'-0" from a wall).

B — For angles 0

°

 to 39

°

 minimum B = 8'-0".

For angles 40

°

 to 45

°

 minimum B = 9'-0".

For angles 46

°

 to 60

°

 minimum B = 9'-6".

Maximum Listed spacing that the sprinkler was calcu-
lated for.

C — Maximum of 3'-0" vertically from the peak.

F — Acceptable for angles 0

°

 to 60

°

.

G — Minimum of 4", for maximum, refer to “A” and measure

along slope.

B

G

A

A

G

C

• a: minimum:

4"

maximum: one-half the maximum calculated

spacing

• b: minimum:

8'-0"

maximum:    16'-0"

• The minimum lateral distance between sprinklers on
    opposing slopes is 8'-0"

Figure  6 -  Symmetric Sprinkler Location on Opposing Slopes*

The minimum distance between sprinklers on opposing slopes
is measured horizontally, some difficult conditions can be
solved by staggering the sprinklers, thus increasing the
horizontal distance.  Remember to measure along the slope
for “A” and “B”.  For angles greater than 60

°

, verify with

Central's Technical Services Department.

A — NFPA minimum of 4", maximum 1/2 of the Listed spacing

that the sprinkler was calculated for.

B — See “E” for minimum spacing.  Maximum Listed spacing

that the sprinkler was calculated for.

 — Maximum 3'-0" vertically from the peak.

E — NFPA minimum of 8'-0" (when minimum of 8'-0" cannot

be obtained due to   “B”, a baffle must be installed
between these sprinklers to obstruct the     discharge
and prevent cold-solder).  See “B” for maximum.

F — Acceptable for angles 0

°

 to 60

°

.

*  For unequal spacing down from peak, see Figure 8.

A

A

A

A

E

C

B

F

F

OBSOLETE

Содержание CENTRAL BV-R1

Страница 1: ...ls They are to be used in wet pipe residential sprinkler systems for one and two family dwellings and mobile homes per NFPA 13D wet pipe residential sprinkler systems for residential occupancies up to...

Страница 2: ...Pendent UL Specific Application Sloped Ceiling Hydraulic Design Requirements for NFPA 13D NFPA 13R Occupancies For use with Figure 4 Table 1 BV R1 Pendent Recessed Pendent Hydraulic Design Requirement...

Страница 3: ...and with pipe thread sealant applied to the pipe threads hand tighten the sprinkler into the sprinkler fitting Step 3 Wrench tighten the sprinkler using only a BV Sprinkler Wrench 1099 Ref Figure 3 T...

Страница 4: ...inimum of 4 verify G dimension minimum of 4 maximum 1 2 of the Listed spacing that the sprinkler was calculated for i e 18 x 18 spacing is maximum of 9 0 from a wall B For angles 0 to 39 minimum B 8 0...

Страница 5: ...he minimum distance between sprinklers is measured horizon tally shown as dimension E Staggering the sprinklers will help maintain minimum horizontal distances in difficult situations Dimensions A and...

Страница 6: ...secting a Flat Ceiling First verify that D is Acceptable or Obstructed per Figure 13 If Acceptable Figure 11 applies If Ob structed additional sprinklers will be necessary to protect the flat ceiling...

Страница 7: ...s Obstructed 10 15 20 25 30 35 40 45 Acceptable 20 x 20 18 x 18 16 x 16 14 x 14 12 x 12 The Central Model BV R1 must be maintained and serviced in accordance with the following instructions NOTES Wet...

Страница 8: ...standards of the National Fire Protection Association e g NFPA 25 in addition to the standards of any other authorities having jurisdiction The installing contractor or sprinkler manufacturer should b...

Отзывы: