qualified inspection service.  Length of
time between such inspections can
vary due to accessibility, ambient
atmosphere, water supply, and site
activity.

Do not attempt to reassemble or

otherwise reuse a sprinkler that has
operated.  Replace any sprinkler
exhibiting corrosion or damage;
always use new sprinklers of the
same type and temperature rating as
replacements.

Do not attempt to replace sprinklers

without first removing the fire protec-
tion system from service.  Be certain
to secure permission from all 

Authori-

ties Having Jurisdiction, and notify all
personnel who may be affected during
system shutdown.  A fire watch during
maintenance periods is a recom-
mended precaution.

To remove the system from service

mode, first refer to the system operat-
ing guide and valve instruction.  Drain
the water and relieve pressure in the
pipes.  Remove the existing unit and
install the replacement, using only the
special sprinkler wrench.  Be certain
to match model, style, orifice, and
temperature rating.

A fire protection system that has

been shut off after an activation
should be returned to service immedi-
ately. Inspect the entire system for
damage and replace or repair as
necessary.  Sprinklers that did not
operate but were subjected to corro-
sive elements of combustion or
excessive temperatures should be
inspected, and replaced if need be.
The 

Authority Having Jurisdiction will

detail minimum replacement require-
ments and regulations.
Guarantee:  Central Sprinkler Com-
pany will repair and/or replace any

products found to be defective in
material or workmanship within a
period of one year from the date of
shipment. Please refer to the current
Price List for further details of the
warranty.

Ordering
Information

Ordering Information:  When
placing an order, indicate the full
product name.  Please specify the
quantity, model, style, orifice size,
temperature rating, type of finish or
coating, and sprinkler wrench.

Availability and Service:  Central
sprinklers, valves, accessories, and
other products are available through-
out the U.S. and Canada, and
internationally, through a network of
Central Sprinkler distribution centers.
You may write directly to Central
Sprinkler Company, or call (215) 362-
0700 for the distributor nearest you.

Patents:  Patents are pending.

Conversion Table:
1 inch = 25.400 mm
1 foot = 0.3048 M
1 pound = 0.4536 kg
1 foot pound = 1.36 Nm
1 psi = 6.895 kpa

= 0.0689 bar
= 0.0703 kg/cm

2

1 U.S. gallon = 3.785 dm

3

= 3.785 liters

Conversions are approximate.

OPTIMA™ is a registered trademark of
Central Sprinkler Company.

Care &
Maintenance

Sprinklers must be handled care-

fully.  They should not be transported
or stored where ambient temperature
may exceed 150

°

F/65.5

°

C.  For best

results, store them in a dry, cool
location in the original shipping
package.

Do not install sprinklers that have

been dropped or visibly damaged.
Sprinklers should never be painted,
coated, plated, or altered in any other
way from manufactured condition or
they may not function properly.  Any
sprinklers altered in such manner
must be replaced.

The owner is responsible for the

proper operating condition of all fire
protection devices and accessories.
The NFPA Standard 25 entitled,
“Inspection Testing and Maintenance
of Water-Based Fire Protection
Systems”, contains guidelines and
minimum maintenance requirements.
Furthermore, the local 

Authority

Having Jurisdiction may have addi-
tional regulations and requirements
for maintenance, testing, and inspec-
tion that must be obeyed.

It is advisable to have sprinkler

systems inspected regularly by a

Central Sprinkler Company

451 North Cannon Avenue, Lansdale, PA 19446

PHONE (215) 362-0700

FAX (215) 362-5385

OBSOLETE

Содержание CENTRAL Attic BB1

Страница 1: ...rios Full scale tested for Listing in wood truss construction Listed for specific pitches of roof slope The Attic Sprinklers provide the best level of protection and control cost by eliminating the ne...

Страница 2: ...in the attic to feed the wet system ceiling sprinklers on the floor below there must be 6 of insulation covering the pipe extending 12 on each side away from the centerline of the pipe and the area a...

Страница 3: ...op of the pipe and the area above must be protected by Attic Sprinklers see figure 10 Insulation is for fire protection purposes It is not freeze protection BlazeMaster CPVC must be installed in accor...

Страница 4: ...40 to more than 30 35 39 0 5 6 7 12 to less than 10 12 SD3 40 to more than 30 35 39 0 5 6 10 12 to 12 12 SD1 30 to more than 10 25 20 0 5 6 4 12 to less than 7 12 SD2 30 to more than 10 25 20 0 5 6 7...

Страница 5: ...al Directional Attic Sprinkler Branch Line Ceiling Truss Ridge 4 0 minimum 6 0 maximum Attic Sprinklers Attic Sprinkler 16 minimum 22 maximum Span Dimension Single Directional Standard Sprinkler Singl...

Страница 6: ...al the maximum spacing is 6 0 and the minimum is 4 0 see figures 2 11 The reason 400 square feet is not an issue with the single directional is because at its maximum spacing 6 0 on center covering 40...

Страница 7: ...all as shown see figure 12 for joists perpendicular to outside wall Ridge Single Directional Attic Sprinkler Outside Wall 40 0 maximum 3 0 max on slope Back to Back Attic Sprinkler 6 0 Max 6 0 Max Be...

Страница 8: ...low the sprinkler there must be 6 clearance over the top of the obstruction to allow water to pass both over and under the obstruction The 6 is measured perpendicular to the slope from the bottom of t...

Страница 9: ...ers 31 0 away from the corner Figure 14 If the attic has noncombustible insulation on the ceiling below the attic sprinklers the area of coverage is mea sured from the top of the insulation Maximum Di...

Страница 10: ...or Single Directional The HIP Sprinkler is located along the slope down the hip and throws a 90 pattern toward the outside eaves This allows the water to corner the fire and control it even at far di...

Страница 11: ...8 4 Attics Having HIP Roofs with the HIP Joists Parallel to Outside Wall The design area requirements of NFPA 13 shall apply to all sprinkler types see Fig 11 5 Attics having a Width Greater than 60 f...

Страница 12: ...rranty Ordering Information Ordering Information When placing an order indicate the full product name Please specify the quantity model style orifice size temperature rating type of finish or coating...

Отзывы: