background image

11

Hydraulic Calculations

Attic sprinklers must be calculated in conformance with these
guidelines.  In all cases, the design area shall include the most
hydraulic demanding sprinklers.  More than one set of
calculations may be required to prove different situations.

1.  Attics Protected Entirely with Back to Back Attic Sprinklers -

For wet systems, calculate the most demanding 5 sprinklers.
For dry systems, calculated the most demanding 7 sprinklers
(see Fig. 16).

2.  Attics Protected Entirely with a Mixture of Back to Back and

HIP Attic Sprinklers - For wet systems, calculate the most
demanding 5 sprinklers.  For dry systems, calculate the most
demanding 9 sprinklers with a maximum of 7 to be back to
back sprinklers (see Fig. 17).

3.  Attics Protected with Single Directional Attic Sprinklers - For

wet systems, calculate the most demanding 5 sprinklers.  For
dry systems, calculate the most demanding 9 single directional
attic sprinklers or standard sprinkers, whichever is more
demanding (see Fig. 18).

4.  Attics Having HIP Roofs with the HIP Joists Parallel to Outside

Wall - The design area requirements of NFPA 13 shall apply to
all sprinkler types (see Fig. 11).

5.  Attics having a Width Greater than 60 ft., but in no Case

Greater than 80 ft. - For attics having HIP roofs with joists
parallel to outside wall, the requirements in Item 4 above
apply.  For other attics, the requirements in Items 1 or 2 above
shall be used plus two additional standard type sprinklers
installed along the eave included in the calculation (see Fig.
19).

Example:  Calculate the 9 most demanding single
directional attic sprinklers.

Figure 18

Single Directional Example

(Dry System Shown)

Wall

Wall

Example:  When mixing back to back and standard
sprinklers at the eave, calculate the 7 most demanding
back to back sprinklers for dry systems or 5 most de-
manding for wet systems, plus the most demanding 2
additional standard sprinklers at the eave.

Figure 19

Attics Greater Than 60 Ft.

(Dry System Shown)

Figure 16

Back to Back Calculation Example

(Dry System Shown)

Example:  Calculate the 7 most demanding back to
back sprinklers along the ridge.

Ridge

Figure 17

Mixed Attic Sprinkler Example

(Dry System Shown)

OBSOLETE

Содержание CENTRAL Attic BB1

Страница 1: ...rios Full scale tested for Listing in wood truss construction Listed for specific pitches of roof slope The Attic Sprinklers provide the best level of protection and control cost by eliminating the ne...

Страница 2: ...in the attic to feed the wet system ceiling sprinklers on the floor below there must be 6 of insulation covering the pipe extending 12 on each side away from the centerline of the pipe and the area a...

Страница 3: ...op of the pipe and the area above must be protected by Attic Sprinklers see figure 10 Insulation is for fire protection purposes It is not freeze protection BlazeMaster CPVC must be installed in accor...

Страница 4: ...40 to more than 30 35 39 0 5 6 7 12 to less than 10 12 SD3 40 to more than 30 35 39 0 5 6 10 12 to 12 12 SD1 30 to more than 10 25 20 0 5 6 4 12 to less than 7 12 SD2 30 to more than 10 25 20 0 5 6 7...

Страница 5: ...al Directional Attic Sprinkler Branch Line Ceiling Truss Ridge 4 0 minimum 6 0 maximum Attic Sprinklers Attic Sprinkler 16 minimum 22 maximum Span Dimension Single Directional Standard Sprinkler Singl...

Страница 6: ...al the maximum spacing is 6 0 and the minimum is 4 0 see figures 2 11 The reason 400 square feet is not an issue with the single directional is because at its maximum spacing 6 0 on center covering 40...

Страница 7: ...all as shown see figure 12 for joists perpendicular to outside wall Ridge Single Directional Attic Sprinkler Outside Wall 40 0 maximum 3 0 max on slope Back to Back Attic Sprinkler 6 0 Max 6 0 Max Be...

Страница 8: ...low the sprinkler there must be 6 clearance over the top of the obstruction to allow water to pass both over and under the obstruction The 6 is measured perpendicular to the slope from the bottom of t...

Страница 9: ...ers 31 0 away from the corner Figure 14 If the attic has noncombustible insulation on the ceiling below the attic sprinklers the area of coverage is mea sured from the top of the insulation Maximum Di...

Страница 10: ...or Single Directional The HIP Sprinkler is located along the slope down the hip and throws a 90 pattern toward the outside eaves This allows the water to corner the fire and control it even at far di...

Страница 11: ...8 4 Attics Having HIP Roofs with the HIP Joists Parallel to Outside Wall The design area requirements of NFPA 13 shall apply to all sprinkler types see Fig 11 5 Attics having a Width Greater than 60 f...

Страница 12: ...rranty Ordering Information Ordering Information When placing an order indicate the full product name Please specify the quantity model style orifice size temperature rating type of finish or coating...

Отзывы: