M.E-2009.E-1DB2
3/25/07 – rev. 5/28/09
E-1DB2 CONTROLLER
2.5.2.9 Connect
the
Neutral
wire from sidelight wiring to
TB1-12.
2.5.2.10 Connect the
Red
wire from sidelight wiring to
TB1-13
.
2.5.2.11 Connect the ground wire (if cable is used) from sidelight wiring to
ground screw right of TB1.
2.6
ALARM WIRING
Individual alarm contacts (Form C) are provided for strobe failures, power failure,
and photocell on. It is left up to the customer or installer on how they choose to
utilize these contacts with their monitoring equipment. External monitoring
equipment is available. Please inquire within the sales staff at the factory for models
available and pricing. Alarm configurations are shown on drawings H40-329, and
M01-329.
2.6.1 White Strobe Failure (SF)
Connect the customer's alarm common to plug J3, terminal #5. Connect the
customer's alarm wire to plug J3, terminal #4, for normally open (or) terminal
#6, for normally closed monitoring.
2.6.2 Red Strobe Failure (RF)
Connect the customer's alarm common to plug J3, terminal #11. Connect
the customer's alarm wire to plug J3, terminal #10, for normally open (or)
terminal #12, for normally closed monitoring.
2.6.3 Power Failure (PF)
Connect the customer's alarm common to plug J3, terminal #14. Connect
the customer's alarm wire to plug J3, terminal #15, for normally open (or)
terminal #13, for normally closed monitoring.
2.6.4 Photocell
(PC)
Connect the customer's alarm common to plug J3, terminal #8. Connect the
customer's alarm wire to plug J3, terminal #7, for "off" operation (or) terminal
#9, for "on" operation monitoring.
6
Содержание E-1DB2
Страница 18: ...M E 2009 E 1DB2 3 25 07 rev 5 28 09 13 ...
Страница 33: ......
Страница 34: ......
Страница 35: ......
Страница 36: ......
Страница 37: ......
Страница 38: ......
Страница 39: ......
Страница 40: ......
Страница 41: ......
Страница 42: ......
Страница 43: ......
Страница 44: ......
Страница 45: ......
Страница 46: ......
Страница 47: ......
Страница 48: ......