Installation
Indications,
functions and options
Messages
Commissioning
Operation and function
Internal backup heating
Opt. functions / Add new function / Backup heat.int.
Adjustment channel Description
Adjustment range / selection Factory setting
Ton
Switch-on temperature
20 … 74 °C
40 °C
Toff
Switch-off temperature
21 … 75 °C
45 °C
Timer
Timer option
Yes, No
No
Funct.
Activation / Deactivation Activated, Deactivated
Activated
Save function / De-
lete function
Save / Delete function
-
-
The internal backup heating function is used for operating the electrothermal
station for backup heating with current from the mains. For this purpose, the power
stages of the power unit and the pump (R1) switch on. The switch-on and switch-off
temperatures Ton and Toff are used as reference parameters.
If the temperature falls below the adjusted threshold Ton, the power stages and the
relay switch on. They switch off, if the temperature exceeds Toff.
S3 is used as the reference sensor (non adjustable).
Note:
For information on timer adjustment see page 13.
External backup heating
Opt. functions / Add new function / Backup heat.ext.
Adjustment channel Description
Adjustment range / selection Factory setting
Ton
Switch-on temperature 20 … 84 °C
40 °C
Toff
Switch-off temperature 21 … 85 °C
45 °C
Timer
Timer option
Yes, No
No
Funct.
Activation / Deactivation Activated, Deactivated
Activated
Save function / Delete
function
Save / Delete function
-
-
The external backup heating function is used for operating the electrothermal
station for backup heating by means of an external heat source (e.g. heat pump, solid
fuel boiler). The switch-on and switch-off temperatures Ton and Toff are used as
reference parameters.
If the temperature falls below the adjusted threshold Ton, R2 energises at 100 %. It
switches off, if the temperature exceeds Toff.
S3 is used as the reference sensor (non adjustable).
Note:
For information on timer adjustment see page 13.