Installation
Indications,
functions and options
Messages
Commissioning
Operation and function
Note:
The controller will only recognise a firmware update file if it is stored in a
folder named ETHERM on the first level of the MicroSD card.
Î
Create a folder named ETHERM on the SD card and extract the
downloaded ZIP file into this folder.
Starting the logging
Î
Insert the MicroSD card into the slot.
Î
Adjust the desired logging type and interval.
Logging will start immediately.
Completing the logging process
Î
Select the menu item Remove card....
Î
After Remove card is displayed, remove the card from the slot.
When Linear is adjusted in the logging type adjustment channel, data logging will
stop if the capacity limit is reached. The message Card full will be displayed.
If Cyclic is adjusted, the oldest data logged onto the SD card will be overwritten as
soon as the capacity limit is reached.
Note:
Because of the increasing size of the data packets, the remaining logging
time does not decrease linearly. The data packet size can increase, e. g. with
the increasing operating hours value.
Storing controller adjustments
Î
To store the controller adjustments on the MicroSD card, select the menu item
Save adjustments.
While the adjustments are being stored, first Please wait..., then Done will be
indicated on the display. The controller adjustments are stored as a .SET file on the
MicroSD card.
Loading controller adjustments
Î
To load controller adjustments from a MicroSD card, select the menu item
Load adjustments.
The File selection window will appear.
Î
Select the desired .SET file.
While the adjustments are being loaded, first Please wait...., then Done will be
indicated on the display.
Note:
To safely remove the MicroSD card, always select the menu item Remove
card... before removing the card.
4.11 Manual mode
Manual mode
Adjustment channel Description
Adjustment range /
selection
Factory setting
Relay 1 … 4
Operating mode selection
Auto, Max, Off, On Auto
All relays...
Operating mode of all relays
Auto, Off
Auto
Stage 1
Manual mode selection for stage 1
(power unit), modulating
Auto, 0 … 100 %
(in steps of 10 %)
Auto
Stage 2, 3
Manual mode selection for stages 2,
3 (power unit)
Auto, 0 %, 100 %
Auto
In the Manual mode menu, the operating modes of the pump relay and stages of
the power unit respectively can be adjusted.
In the menu item All relays..., all relays can simultaneously be switched off (Off) or
set to automatic mode (Auto):
Off = Relay is switched off (manual mode)
Auto = Relay is in automatic mode
The operating mode can be selected for each individual relay, too. The following
options are available:
On = Relay active at 100 % speed (manual mode)
Off = Relay is switched off (manual mode)
Max = Relay active at maximum speed (manual mode)
Auto = Relay is in automatic mode