7
Storage
If your dispenser is to be stored for a period of time, clean it thoroughly. This will help protect
the dispenser from possible damage.
Troubleshooting
The following troubleshooting guide is designed to help you with basic diagnostics and repairs
if you should encounter abnormal service from your FR902 series dispenser. We recommend
you use only genuine Fill-Rite parts. These parts, and additional service information is
available through your authorized Fill-Rite dealer.
Further troubleshooting information can be found in your pump manual. If you need additional
assistance, please contact us at 1-800-634-2695 (M-F 8 AM–5 PM ET).
Concern
Possible Cause
Recommended Repair
Counter inaccurate.
Dispenser mis-
calibrated.
Check calibration and recalibrate as
necessary (directions on page 6).
Air in lines or dispenser
chamber.
Check line seals and joints for
leakage; seal leaks appropriately.
Measuring gears or disc
are sticking.
Clean or replace internal dispenser
components as necessary.
Fluid leak.
Dirty or damaged seal or
gasket.
Clean seal or gasket and seat, replace
seal or gasket as necessary.
Low flow capacity.
Clogged meter chamber.
Clean meter chamber; clean or replace
screens and filters in piping.
Plugged filter.
Replace filter element.
Plugged pump.
Inspect and clean pump as necessary.
Meter body cracks.
Excess line pressure.
Install pressure relief valve so high
pressure bleeds back to the tank.
Replace cracked meter body.
Nutating Disc Broken.
Sudden high pressure
fluid hitting disc.
Avoid surge flows by installing a shut-
off valve on outlet of dispenser; install
dispenser as close to the pump as
possible, keep piping full of liquid.
Replace meter chamber assembly.
Fluid Compatibility
The FR902 series dispensers are compatible ONLY with the following fluids:
>Diesel Fuel >Gasoline & Gasoline / Alcohol blends (up to 10% ethanol) >Fuel Oil
>Lubricating Oil (up to 60W lubricating oil; not temperature dependant)
Assembly and Disassembly
The FR902 Series Dispenser cabinet contains a 900 series meter, internal plumbing, and
electrical switch. When referencing “Item Numbers” in each procedure, refer to diagram on
page 9 for dispenser item number parts, and the diagram on page 11 for meter item numbers.
CAUTION!
If in doubt about compatibility of a specific fluid, contact supplier of
fluid to check for any adverse reactions to the following wetted materials:
Ryton
®
Aluminum
Stainless Steel
Fluorocarbon
Buna N