9
V01.0 | 2017/10
6.3
Characteristic data
Value
Standard
Performance Level (PL)
e
EN/ISO 13849-1
Safety category
4
EN/ISO 13849-1
Safety Integrity Level (SIL)
3
IEC/EN 61508
SIL CL
3
EN/IEC 62061
PFH
D
4 × 10
-9
1/h
IEC/EN 61508; EN/ISO 13849-1
PFD
5 × 10
-6
IEC/EN 61508
MTTF
D
> 2500 years
EN/ISO 13849-1: 2016
DC
99 %
Permissible duration of use (TM)
20 years
EN ISO 13849-1
Maximum on-time
12 months
IEC/EN 61508
Max. reaction time in case of shutdown
CIP Safety > local output
25 ms
IEC/EN 61508
Local input > CIP Safety
20 ms
Local input <> local output
35 ms
7
Operating Instructions
7.1
General
➤
➤
In case of a safety application, register the devices under
www.turck.de/SIL
.
➤
➤
Only trained and qualified personnel must mount, install, operate and maintain the devices.
➤
➤
The devices are not specified for a certain application. Make sure that application-specific
aspects are considered.
➤
➤
Replace the devices before the expiration of the permissible duration of use (see
➤
➤
Execute a functional test every twelve months.
➤
➤
The devices must not be repaired. If problems occur with regard to functional safety, notify
Turck immediately and return the devices immediately to:
Hans Turck GmbH & Co. KG
Witzlebenstraße 7
45472 Mülheim an der Ruhr
Germany
➤
➤
In case of device errors which lead to the safe state, take measures which guarantee the safe
state for the further operation of the complete control system.
➤
➤
Report dangerous failures immediately to Turck.