Operating Instructions
Hans Turck GmbH & Co. KG | T +49 208 4952-0 | F +49 208 4952-264 | [email protected] | www.turck.com
7.2.3
Address Assignment
The device has 2 IP addresses. The first IP address addresses the safe (left) functional unit
(C0…C3), the second IP address addresses the non-safe (right) functional unit (C4…C7).
The address setting of both functional units is done via the web server of the safe unit (IP ad-
dress in the state of delivery: 192.168.1.254).
The rotary coding switches at the device set the last byte of the IP address for the safe (left)
functional unit.
➤
➤
Set the last byte of the IP address for the TBIP-L…-FDIO1-2IOL using the 3 rotary coding
switches under the cover at the device.
In the delivery state, the rotary switches are set to 000.
Switch position
Meaning
000
192.168.1.254
1…254
Static rotary, setting of the last byte of the IP address, accept the setting with a
device restart
300
BootP
400
DHCP
500
PGM
600
PGM-DHCP
900
Factory Reset: reset of the device to factory settings
901
Stick Reset: Deletes the content of the memory chip.
7.2.4
Configuring
The safety function of the safe channels can only be configured via the software “Turck Safety
Configurator”.
After the configuration, the device generates a CRC and a validation protocol. This protocol has
to be checked and validated by the user. The CRC is stored as reference in the configuration of
the PLC and guarantees the correct safety function.
Further information can be found in the online help.
The configuration of the safe I/O channels set via the Turck Safety Configuratior is automatically
stored to a pluggable memory stick which is part of the scope of delivery. In case of a device ex-
change, the device configuration can be transferred to another device using the memory stick.
WINK
MS
NS
EtherNet/IP™
ETH1
ETH2
IP Address
0
9 8 7 6
5
4
3
2
1
0
9 8 7 6
5
4
3
2
1
0
9 8 7 6
5
4
3
2
1
x 100
x 10
x 1
Memory
Содержание TBIP-L-FDIO1-2IOL Series
Страница 1: ...Your Global Automation Partner TBIP L FDIO1 2IOL Safety Block I O Module Safety manual Translation...
Страница 2: ...2 Hans Turck GmbH Co KG T 49 208 4952 0 F 49 208 4952 264 more turck com www turck com...
Страница 21: ...28 subsidiaries and over 60 representations worldwide www turck com 100000664 2017 10 100000664...