14
Appendix: Wiring Diagrams
Hans Turck GmbH & Co. KG | T +49 208 4952-0 | F +49 208 4952-264 | [email protected] | www.turck.com
LED
Color
Meaning
4…7
green
Channel active
green blinking
Self-testing (input only)
red
Discrepancy, overload (output only)
red blinking
Cross Connection
8…11
green
Channel active
red
Overload (output only)
red blinking
Channel inactive (input only), overload at supply
green permanent,
red blinking
Channel active and overload at supply (input only)
12…15
green
IO-Link communication or DI active
red
Error
0…7
red all blinking,
alternating
Fatal Error
WINK
white flashing
Helps to localize the module if the Blink/Wink command is active.
7.3.2
Output Error Behavior
In case of an error a switched-off output can be switched on for ≤ 1 ms.
7.3.3
Decommissioning
The decommissioning is described in the user manual (100000718).