Instructions for Use

TBIL-M1-16DXP-B

I/O Hub with IO-Link

Содержание TBIL-M1-16DXP-B

Страница 1: ...Your Global Automation Partner Instructions for Use TBIL M1 16DXP B I O Hub with IO Link...

Страница 2: ...2 Hans Turck GmbH Co KG T 49 208 4952 0 F 49 208 4952 264 more turck com www turck com...

Страница 3: ...unctions and Operating Modes 8 5 Mounting 9 6 Connecting 10 6 1 Connecting the Supply Voltage and IO Link 10 6 1 1 Supply Concept 11 6 2 Connecting Digital Sensors and Actuators 12 7 Using the Device...

Страница 4: ...0 F 49 208 4952 264 more turck com www turck com 9 5 IO Link Events 26 9 6 IO Link Error Codes 26 10 Troubleshooting 27 11 Maintenance 28 12 Repair 28 12 1 Returning Devices 28 13 Disposal 28 14 Tech...

Страница 5: ...ING indicates a dangerous situation with medium risk of death or severe in jury if not avoided CAUTION CAUTION indicates a dangerous situation of medium risk which may result in minor or moderate inju...

Страница 6: ...omagnetic compatibility n 2011 65 EU RoHS II Directive 2 4 Manufacturer and Service Hans Turck GmbH Co KG Witzlebenstra e 7 45472 Muelheim an der Ruhr Germany Turck supports you with your projects fro...

Страница 7: ...e 3 2 General Safety Instructions n The device may only be assembled installed operated parameterized and maintained by professionally trained personnel n The device may only be used in accordance wit...

Страница 8: ...device has the following LED indicators n IO Link communication n I O status 4 2 Properties and Features n Fibre glass reinforced housing n Shock and vibration tested n Fully potted module electronic...

Страница 9: ...four M4 screws on a flat and pre drilled mounting surface Fasten the module to the mounting surface with 4 M4 screws The maximum tightening torque for the screws is 0 5 Nm 107 34 32 2 44 7 M4 4x max...

Страница 10: ...caps 6 1 Connecting the Supply Voltage and IO Link WARNING Defective power supply unit Danger to life due to dangerous voltages on touchable parts Only use SELV or PELV power supplies in accordance w...

Страница 11: ...IO Link channels are separated into the different potential groups detachable I O supplied through V2 and non detach able I O supplied through V1 This allows a safety shutdown of parts of an installat...

Страница 12: ...in assignment TBIL M1 16DXP B C0 C3 8 9 10 11 12 13 14 15 Fig 8 M12 connector for connecting digital sensors and actuators C4 C7 Connect the sensors and actuators to the device according to the pin as...

Страница 13: ...f EN ISO 13849 1 and EN IEC 61508 7 1 1 Safety Characteristic Data for the Galvanic Isolation Characteristic data Value Standard PFHD Average frequency of dangerous failure per hour 5 10 9 1 h IEC EN...

Страница 14: ...he cables is not possible 7 3 2 Switch off Supply Voltage Safely WARNING 1 pole switch off the supply voltage Safe separation not guaranteed Always switch off the supply voltage on both poles 7 3 3 Co...

Страница 15: ...value Comment 0x10 16 Vendor Name read only 16 Turck 0x11 17 Vendor Text read only 32 www turck com 0x12 18 Product Name read only 32 TBIL M1 16DXP B 0x13 19 Product ID read only 16 Ident no of the d...

Страница 16: ...Access Length Byte Meaning 0x40 64 Parameter ID read write 4 Customer specific ID for free use 0x41 65 Inverting Input read write 2 Invert digital input 0x42 66 Activate Output read write 2 Activate...

Страница 17: ...o be set for all connectors of the module via the IODD Activate Output 0x42 66 Sub Index 0 this parameeter activates or deactivates the output function of the digital channel Format Length Byte 1 byte...

Страница 18: ...ub index Sub index 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 C7P2 C7P4 C6P2 C6P4 C5P2 C5P4 C4P2 C4P4 C3P2 C3P4 C2P2 C2P4 C1P2 C1P4 C0P2 C0P4 NOTE This parameter can also be set for all connectors of the...

Страница 19: ...channel Default values are shown in bold Value Meaning 00 0 Set output to 0 01 1 Set output to 1 10 Current value Hold current value 11 reserved Byte 3 Byte 2 Byte 1 Byte 0 Bit offset Bit offset Bit o...

Страница 20: ...e Additionally it defines the threshold values for undervoltage diagnostics for V1 and V2 Format Length Array of Bytes 2 byte 2 bit per module The default values are written in bold Value Meaning Acti...

Страница 21: ...tics 2 Group diagnos tics Under voltage V2 Under voltage V1 Connector diagnostics overcurrent sensor supply 3 Overcur rent C7 Overcur rent C6 Overcur rent C5 Overcur rent C4 Overcur rent C3 Overcur re...

Страница 22: ...ndervoltage Vx 0 No diagnostic message 1 Undervoltage of supply voltage V1 and V2 Connector diagnostics overcurrent sensor supply Overcurrent Cx 0 No diagnostic mes sage 1 Overload at the sensor actua...

Страница 23: ...ule error Red flashing 1 Hz IO Link communication error free invalid process data or diagnostic message Off no voltage supply 9 3 2 Channel LEDs LED 0 15 Meaning input Meaning output Green Input activ...

Страница 24: ...ostics pending at the module n Undervoltage V1 per module n Undervoltage V2 per module n Overcurrent sensor supply per connector Format Length Array of Bytes 2 byte 0 no diagnostics 1 diagnostic messa...

Страница 25: ...stics 1 diagnostic message Byte 0 Bit offset 7 6 5 4 3 2 1 0 Overcur rent C3P2 Overcur rent C3P4 Overcur rent C2P2 Overcur rent C2P4 Overcur rent C1P2 Overcur rent C1P4 Overcur rent C0P2 Overcur rent...

Страница 26: ...he sensor supply at one of the connectors C0 C7 or overcurrent at one of the outputs DO0 DO15 The mapped diagnostics in the process image of the inputs show which slot or output detects an overcurrent...

Страница 27: ...irst check whether ambient interference is present If there is no ambient interference present check the connections of the device for faults If there are no faults there is a device malfunction In th...

Страница 28: ...ust be decommissioned if it is faulty Observe our return acceptance conditions when returning the device to Turck 12 1 Returning Devices Returns can only be accepted if a declaration of decontaminatio...

Страница 29: ...1 2 Type of input diagnostics Type of input diagnostics Signal voltage low level 3 5 VDC EN 61131 2 type 1 and 3 Signal voltage high level 11 30 VDC EN 61131 2 type 1 and 3 Input delay 2 5 ms Max inpu...

Страница 30: ...pple According to IEC 60068 2 31 IEC 60068 2 32 Electro magnetic compatibility According to EN 61131 2 6 4 Approvals CE cULus General Information Dimensions B L H 54 150 27 4 mm Operating temperature...

Страница 31: ...gen der folgenden EU Richtlinien durch Einhaltung der folgenden Normen gen gen to which this declaration relates are in conformity with the requirements of the following EU directives by compliance wi...

Страница 32: ...Over 30 subsidiaries and over 60 representations worldwide www turck com 100003088 2018 11 100003088...