Operating
Evaluating diagnostic data
174
Hans Turck GmbH & Co. KG | T +49 208 4952-0 | F +49 208 4952-264 | [email protected] | www.turck.com
TBEN-S2-8DIP – diagnostic data mapping
Byte
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
n
-
-
-
-
VERR V1
C3
VERR V1
C2
VERR V1
C1
VERR V1
C0
n + 1
-
-
-
-
-
-
-
-
PROFINET error codes
Station diagnostics (slot 0)
PROFINET diagnostics
Diagnostics
Error code
Channel
Undervoltage
V1
0x0002
0
V2
0x0002
1
I/O diagnostics (slot 1)
PROFINET diagnostics
Diagnostics
Connector/pin
Error code
Channel
Overcurrent supply group
Overcurrent supply VAUX1 at channel 0…3
VERR V1 C0
C0P1
0x01D0
0
VERR V1 C1
C1P1
0x01D1
0
VERR V1 C2
C2P1
0x01D2
0
VERR V1 C3
C3P1
0x01D3
0
TBEN-S1-8DIP-D – diagnostic data mapping
Byte
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
n
VERR V1
ch7
VERR V1
ch6
VERR V1
ch5
VERR V1
ch4
VERR V1
ch3
VERR V1
ch2
VERR V1
ch1
VERR V1
ch0
n + 1
-
-
-
-
-
-
-
-
PROFINET error codes
Station diagnostics (slot 0)
PROFINET diagnostics
Diagnostics
Error code
Channel
Undervoltage
V1
0x0002
0
V2
0x0002
1
I/O diagnostics (slot 1)
PROFINET diagnostics
Diagnostics
Connector/pin
Error code
Channel
Overcurrent supply group
Overcurrent supply VAUX1 at channel x
VERR V1 ch0
C0
0x0100
0
VERR V1 ch1
C1
0x0101
0
VERR V1 ch2
C2
0x0102
0
VERR V1 ch3
C3
0x0103
0
VERR V1 ch4
C4
0x0104
0
VERR V1 ch5
C5
0x0105
0
VERR V1 ch6
C6
0x0106
0
VERR V1 ch7
C7
0x0107
0
Содержание TBEN-S Series
Страница 1: ...Your Global Automation Partner Instructions for Use TBEN S Digital and Analog Modules ...
Страница 2: ...2 Hans Turck GmbH Co KG T 49 208 4952 0 F 49 208 4952 264 more turck com www turck com ...
Страница 29: ...V04 00 2021 05 29 Analog modules V1 V2 V1 V2 Fig 36 Power supply TBEN S2 4AI Fig 37 Power supply TBEN S2 4AO ...
Страница 244: ...Over 30 subsidiaries and over 60 representations worldwide www turck com 100001931 2021 05 100001931 ...