Commissioning
Commissioning the device in PROFINET
36
Hans Turck GmbH & Co. KG | T +49 208 4952-0 | F +49 208 4952-264 | [email protected] | www.turck.com
A
B
C
Fig. 35: TBEN-L5-8IOL – slot overview in TIA-Portal (example)
A Basic slot for e. g. DXP-channels and Data Valid Signal
B
IO-Link ports for the configuration with specific IO-Link devices or for generic configura-
tion
C
one slot each for diagnostics and status
8.6.3
Address setting in PROFINET
In IP-based communication, the field devices are addressed by means of an IP address.
PROFINET uses the Discovery and Configuration Protocol (DCP) for IP assignment.
When delivered, each field device has, among other things, a MAC address. This information is
sufficient to give the respective field device a unique name.
The address is assigned in two steps:
n
Assignment of a unique plant specific name to the respective field device.
n
Assignment of the IP address from the IO-Controller before the system start-up based on the
plant-specific (unique) name.
Содержание TBEN-L 8IOL Series
Страница 1: ...Your Global Automation Partner Instructions for Use TBEN L 8IOL IO Link Master Module ...
Страница 2: ...2 Hans Turck GmbH Co KG T 49 208 4952 0 F 49 208 4952 264 more turck com www turck com ...
Страница 148: ...Over 30 subsidiaries and over 60 representations worldwide www turck com D301407 2019 10 D301407 ...