V02.00 | 2019/10
99
IO-Link Port Class (VSC 137)
This class provides one instance per IO-Link port at the IO-Link master module.
Attr. no.
Designation
Get/
set
Type
Meaning
Dec. Hex.
Parameters
1
0x01 Operation mode
G/S USINT
0 = IO-Link without validation
1 = IO-Link with family compatible device
2 = IO-Link with compatible device
3 = IO-Link with identical device
4 = DI (with parameter access)
5…7 = reserved
8 = DI
2
0x02 Data Storage Mode
G/S USINT
0 = activated
1 = overwrite
2 = read in
3 = deactivated, clear
3
0x03 Cycle time
G/S USINT
See [
4
0x04 Revision
G/S USINT
0 = automatic
1 = V 1.0
5
0x05 Activate Quick Start-
Up
G/S USINT
0 = no
1 = yes
6
0x06 Device parameteriza-
tion via GSD
G/S USINT
0 = no
1 = yes
7
0x07 Evaluating Process In-
put Data
G/S USINT
0 = diagnostics generated
1 = no diagnostic generated
8
0x08 Deactivate diagnostics G/S USINT
0 = no
1 = notifications
2 = notifications and warnings
3 = yes
9
0x09 Process input data
mapping
G/S USINT
0 = direct
1 = swap16 bit
2 = swap 32 bit
3 = swap all
10
0x0A Process output data
mapping
G/S USINT
0 = direct
1 = swap16 bit
2 = swap 32 bit
3 = swap all
11
0x0B Vendor ID
G/S USINT
0 = inactive
1 = active
12
0x0C Device ID
G/S USINT
0 = inactive
1 = active
Diagnostics
13
0x0D Wrong or missing
device
G
USINT
0 = inactive
1 = active
14
0x0E Data storage error
G
USINT
0 = inactive
1 = active
15
0x0F Evaluating Process In-
put Data
G
USINT
0 = inactive
1 = active