Setting
Setting via teach adapter
22
Hans Turck GmbH & Co. KG | T +49 208 4952-0 | F +49 208 4952-264 | [email protected] | www.turck.com
Window function – setting the switching range
Window function
Out2
Out1
GND/T1 > 8 s
13 s
LED GN 2 × 1 Hz
GND/T1 > 8 s
13 s
LED YE 2 × 1 Hz
Measure and save
SP1
Fail
LED GN/YE
1.5 s × 5 Hz
GND/T1 > 2 s
7 s
LED GN 1 × 1 Hz
GND/T1 > 2 s
7 s
LED GN 1 × 2 Hz
Measure and save
SP2
OK
LED GN
1.5 s × 5 Hz
Normal
operation
U
B
/T2 > 2 s
LED YE
1 × 8 Hz
Cancel
Fig. 22: Window function – setting the switching range
Connect the TX1-Q20L60 teach adapter between the sensor and the connection cable.
Position the object for switching point 1.
Select the switching output.
Store switching point 1: Press and hold down the pushbutton on the adapter to GND for
8…13 s.
Position the object for switching point 2.
Store switching point 2: Press and hold down the pushbutton on the adapter to GND for
2…7 s.
a
The switching points have been successfully taught in if the green LED flashes for 1.5 s at
a frequency of 5 Hz.