Push button

 on the teach adapter 

 on the teach adapter 

 on the teach adapter 

 on the teach adapter 

 on the teach adapter 

or TEACH line

Step 1

Press and hold button for 2 s (connect TEACH line to "+").

Step 2

After 2 s the sensor changes into the teach mode and first filling state is taught.

Release the button (disconnect TEACH line from "+").

Step 3

Wait at least 2 s to teach the second filling level. Press button (or connect TEACH line to "+“) and the second

filling state is taught. This may not take more than 2 s. After a successful teach-in, the sensor returns to its RUN

mode and the values just taught are stored.

Failed TEACH procedure

If the sensor is not capable of adjusting to the second filling level after completing the TEACH procedure (max.

2 s), the green and yellow LEDs flash alternately to indicate the failure. After 3 s the sensor returns to step 2. In

order to return to the RUN mode and to cancel the TEACH mode press the button for more than 5 s (connect

TEACH line to "+“); the values taught will not be saved. After cancelling the TEACH-mode it is possible to

change the operating mode and start a new TEACH procedure.

LED-indication

green short OFF, then ON

green and yellow flash

alternately

green or yellow

depending on operating

status (RUN mode)

green and yellow rapidly

flash alternately

(failed teach)

levelprox 

non-invasive ultrasonic level sensor

LPRE-M30-AP6X2-H1141

Changing the operating mode

Push button on TEACH adapter VB2-SP1

 

or TEACH line

Step 1

Press push button for 5 s (connect TEACH line to "+“ ) and hold. (Prior to going into the PARAMETER mode, the

sensor temporarily goes into the TEACH mode).

Step 2

After 5 s the sensor is in the PARAMETER mode. By pressing and releasing the push button (connect to and

disconnect TEACH line from "+“) you will toggle between the two operating modes, i.e. the echo and the

reverberation mode. The PARAMETER mode is quit by pressing the button (connect TEACH line to "+“) for more

than 5 s. The sensor retains the operating mode last selected. Should operation not be possible after changing

the operating mode, this will be indicated by quick alternate flashing of the LED (see below). Change mode and

re-teach filling states.

LED Indications

short OFF and

then green; after 2 s

alternately green and yellow

(TEACH mode)

alternately green and yellow

depending on mode:

– long yellow and short green

(reverberation)

– long green and short yellow

(echo)

TEACH-IN of Liquid Levels

In order to detect filling states reliably, the 

levelprox

 sensor must be adjusted to the specific mounting conditions, such as the wall thickness and

dimensions. For this, the sensor has to learn to differentiate between two different filling states. In the non-actuated state, the liquid level must be at

least 5 cm below and in the actuated state at least 3 cm above the sensor centre when presenting the two different conditions. The sensor

automatically carries out the necessary adjustments (programming the respective filing states) on request.

The order in which the different liquid levels are presented is not of importance. If the sensor is removed  and re-mounted, or if the operating mode is

changed, repeated teach-in is necessary. This is also recommended when re-mounting the sensor in the same position. The TEACH procedure

(programming the filling states) is initiated by connecting the teach line to "+". The TEACH procedure can be facilitated by using the teach adapter

VB2-SP1 which is plugged between the sensor and the connection cable. The TEACH procedure can then be carried out via the push button. After

completing the TEACH procedure, the adapter can be removed.

Sensor performance in the event of an error

Insufficient acoustic coupling to the container, electric or acoustic interferences, taught echo missing

(echo mode is default setting)

LED Indication

green and yellow rapidly

flash alternately