Setting
Setting via touchpads
Hans Turck GmbH & Co. KG | T +49 208 4952-0 | [email protected] | www.turck.com
V02.00 | 2022/08 | 22
9.2.3
Quick-Teach — setting the current flow speed as the switching point
With the Quick-Teach function, the current flow speed can be directly taught in as the switch-
ing point FLOW for devices with a switching output; setting a separate MAX/MIN indicated
range is not required.
The Quick-Teach function for teaching in the switching point is marked in the flow chart with
1
.
Menu
LED indicator bar
Setting the current flow speed as the switching point
1
Operate the flow speed in the application at the upper limit
value.
2
To access the menu from display mode: Press [ENTER]
once.
ð
DeltaFlow active: LED 11 in the LED bar is flashing
yellow. System has not yet stabilized.
Wait until the LED is flashing green.
Once the LED bar is flashing green, the system has sta-
bilized: Press [ENTER] for 3 s until only LED 6 is flashing
yellow.
a
The current flow speed is taught in as the switching
point.
3
Optional: Change the switching point incrementally by 0.5 %:
Increase the switching point incrementally by 0.5 % of
the measuring range end value: Press [SET].
Reduce the switching point incrementally by 0.5 % of
the measuring range end value: Press [MODE].
4
Store the switching point: Press [Enter].
a
LED bar briefly flashes green twice.
2x
9.2.4
MAX/MIN teach-in — setting the switching point for flow
With the MAX/MIN teach-in function, the FLOW switching point is taught in as a percentage
value within an adjustable MAX/MIN indicated range for devices with a switching output.
The MAX/MIN teach-in function for setting the switching point is marked in the flow chart with
2
.
To open from display mode: Press [MODE] once.
Menu
LED indicator bar
Setting the switching point for flow monitoring
1
Press and hold [SET] for 3 s until the switching point LED first
flashes yellow and then changes to a constant yellow again.
2
Set the switching point:
Increase the switching point incrementally by 9.1 %:
Press [SET].
Reduce the switching point incrementally by 9.1 %:
Press [MODE].
3
Store the switching point:
Press [Enter].
a
LED bar briefly flashes green twice.
2x