Setting
Setting via touchpads
28
Hans Turck GmbH & Co. KG | T +49 208 4952-0 | F +49 208 4952-264 | [email protected] | www.turck.com
9.2.9
Parameters in the EF submenu (Extended Functions)
Explanation
Options
Function
MODE
Measured variable
DIST
Distance to the sensor
DPCT
Distance to the sensor in % (scaled to Full-EMTY)
LVL
Level
LPCT
Level in % (scaled to FuLL-EMTY)
VOL
Volume
VPCT
Volume in % (scaled to FuLL-EMTY)
uniV
Volume unit
A
Liter
m³
Cubic meters
in³
Cubic inch
ft³
Cubic foot
gal
Gallons
uniL
Unit of length
mm
Millimeters
m
Meters
in
Inches
ft
Feet
GEOM
Geometry submenu
For additional setting options for the container
geometry, see the Parameters in the GEOM submenu
table
Hi
Maximum value memory
The highest level is stored and can be displayed/
deleted (hold down [SET]).
Lo
Minimum value memory
The lowest level is stored and can be displayed/
deleted (hold down [SET]).
dSP1…
dSP4
Switch delay of
SP1…SP4
0…60 s in increments of 0.1 s (0 = delay time not
active)
Default: 0.0
drP1…drP4
Switch delay of rP1…rP4
0…60 s in increments of 0.1 s (0 = delay time not
active)
Default: 0.0
dFH1…
dFH4
Switch delay of
FH1…FH4
0…60 s in increments of 0.1 s (0 = delay time not
active), only available with window mode Fno or Fnc
Default: 0.0
dFL1…dFL4
Switch delay of FL1…FL4
0…60 s in increments of 0.1 s (0 = delay time not
active), only available with window mode Fno or Fnc
Default: 0.0
dAP
Damping of switching output
(filter)
Filter for momentary or high frequency measurement
peaks: 0…8 s in increments of 0.01 s (0 = filter is
deactivated)
Default: 0.0
dAA
Damping of analog output
Filter for momentary or high frequency measurement
peaks: 0…8 s in increments of 0.01 s (0 = filter is
deactivated)
Default: 0.0
P-n
Behavior of the switching output
Auto
Automatic detection (NPN/PNP)
NPN
N switching
pnp
P switching