Operation
Display indications
16
Hans Turck GmbH & Co. KG | T +49 208 4952-0 | F +49 208 4952-264 | [email protected] | www.turck.com
8
Operation
8.1
LEDs – operation
LED
Indication
Meaning
PWR
Green
Device is operational
Green flashing
IO-Link communication
FLT
Red
Error
DST
Green
Distance between the sensor and the surface in % or selected unit
LVL
Green
Level display in % or selected unit
VOL
Green
Filling volume in % or selected unit
SSI
Yellow flashing
(1 Hz)
Signal strength ≤ 20 %
Yellow flashing
(2 Hz)
Signal strength > 20 % ≤ 40 %
Yellow flashing
(4 Hz)
Signal strength > 40 % ≤ 60 %
Yellow
Signal strength > 60 % ≤ 80 %
Green
Signal strength > 80 %
PCT
Off
Display of the selected unit
Green
Displayed in %
LOC
Yellow
Device locked
Yellow flashing “Lock/unlock” process active
Off
Device unlocked
I
Yellow
Switching output 1 active
II
Yellow
Switching output 2 active
8.2
Display indications
Display
Meaning
d-OR
Value not displayable (> 9999)
d-UR
Value not displayable (< -1999)
Err
Unspecified, internal error
ErrG
Incorrect geometrical information on the dimensions of the medium container
ErrL
Burden at the analog output outside of the permissible range
ErrT
No object detected
SC
Short circuit
Loc
Device locked
uLoc
Device unlocked
- - - -
Sensor failure
Содержание 100012722
Страница 1: ...Your Global Automation Partner Instructions for Use LRS510 Radar Level Sensors...
Страница 2: ...2 Hans Turck GmbH Co KG T 49 208 4952 0 F 49 208 4952 264 more turck com www turck com...
Страница 48: ...Over 30 subsidiaries and over 60 representations worldwide www turck com 100018911 2021 07 100018911...