Installing
Mounting the sensor in hygienic applications according to EHEDG
12
Hans Turck GmbH & Co. KG | T +49 208 4952-0 | F +49 208 4952-264 | [email protected] | www.turck.com
5.2
Mounting the sensor with the process adapter
The sensor is equipped with a G1/2” thread and is self-sealing when used in combination with
the process adapter. An additional seal is not necessary.
Before assembly, ensure that the system has been depressurized and that there is no me-
dia in the pipe or container.
Mount the process adapter on the tank/pipe, ensuring that it is fully sealed.
Screw the sensor into the Turck process adapter.
Use a wrench to tighten the sensor (tightening torque: 20 Nm).
5.3
Mounting the sensor in hygienic applications according to EHEDG
The sensor is certified for use in hygienic applications in accordance with EHEDG.
Integrate the sensor in the plate in accordance with EHEDG requirements.
Only use an EHEDG-compliant process adapter for mounting.
Install the sensor so that there is no dead space. Observe the following dimensions to
avoid dead space: L < (D-d)
d
D
L
A
Fig. 4: Avoiding dead space and installing a leakage hole (A)
Install a self-draining sensor.
Choose an installation in the tank so that the sensor is fully accessible from the cleaning
ports.
Install the leakage hole (A) so that it is clearly visible. When using vertical cables, the leak-
age hole must face downward.
Содержание 100004248
Страница 1: ...Your Global Automation Partner Instructions for Use NCLS Limit Level Sensor...
Страница 2: ...2 Hans Turck GmbH Co KG T 49 208 4952 0 F 49 208 4952 264 more turck com www turck com...
Страница 4: ...Contents 4 Hans Turck GmbH Co KG T 49 208 4952 0 F 49 208 4952 264 more turck com www turck com...
Страница 24: ...Over 30 subsidiaries and over 60 representations worldwide www turck com 100021577 2022 06 100021577...