9.0.0 Operation
9.1.0 Regulating air volume
See also the user guide enclosed for the TX electronic controller.
The unit has 2 operating settings. One for daytime, which gives the dimensioned air
volume the unit is set for by the factory, and one night time operation, which runs slower,
to save energy at night.
NB! If air volume is regulated by a CO2 sensor, the unit will adjust its speed according to
conditions in the room.
9.2.0 Regulating temperature
See also the user guide enclosed for the TX electronic controller.
The temperature required is set on the control panel. We recommend that the temperature
should not be set higher than the room temperature. Fresh air temperature should be 2-3
degrees below room temperature to achieve the best circulation in the room.
When the unit is stopped, the last temperature setting is automatically saved, and the unit
will start using that setting.
The unit has a fully-automatic by-pass system, which directs the air past the exchanger
when the temperature permits.
9.3.0 Master/slave
To use this function, a PCB board is required. Contact your dealer.
5 slaves can be connected to one master. This means that one unit can be used to control
5 other units, so that all 6 units run uniformly.
See the user guide for correct master/slave setup.
The unit is programmed as a master as standard.
NOTE!
Units with electrical comfort heaters always have a run-on time of approx.
80 seconds.