Flow Coefficient Values
- Model STVG
Optional features and accessories available for this
Macon product are an extra charge, and not included
in the standard model price.
www.maconbalancing.com
Tunstall Corporation
118 Exchange Street · Chicopee, MA 01013
Phone (413) 594
-
8695 · Fax (413) 598
-
8109
Section:
Components
Bulletin
-
MB
-
STVG
-
0915
Installation Recommendations for
GROOVED END VALVE CONNECTIONS
Grease the pipe ends, valve ends and rubber gasket lip
with grease, graphite paste or similar grease. Slip the
rubber gasket over the pipe end of each joint. Slide the
gasket past the grooves. Position the grooved end valve
between the pipe ends and slide the gaskets back into the
central spanned position.
All products have a flow direction arrow. Make sure that
it is pointing in the direction of the flow. Apply grease
on the outside of the gasket. Install housing clamps over
the gasket
-
insert bolts and nuts.
Tighten nuts evenly, using socket or other wrench. Tight-
en so that housing clamps come together evenly. The
connection is complete when housing clamps meet metal
to metal. Further tightening of bolts is not necessary.
Pre
-
assemble large diameter multi
-
segment housing
clamps loosely and install them as half
-
housings. Take
up evenly from top to bottom on alternate bolts.
Correction for Liquids
Applies to liquids other than water. Correct the measured
flow (q) by the density (
γ
) according to this formula.
See Figure 4
Sizing a Balancing Valve
When the differential pressure and design flow are
known, use this formula to calculate Cv value.
See Figure 5
Flow coefficient values (Cv's) at various handwheel settings
Handwheel
Setting
2-1/2"
DN 65
3"
DN 80
4"
DN
100
5"
DN
125
6"
DN
150
8"
DN
200
10"
DN
250
12"
DN
300
1.00
8
17
24
81
52
126
250
298
1.25
10
20
27
97
56
162
303
346
1.50
12
22
29
113
59
198
354
452
1.75
15
25
32
129
62
233
399
448
2.00
19
27
35
143
66
274
444
499
2.25
24
30
38
158
70
316
480
553
2.50
30
33
31
171
74
360
513
618
2.75
36
36
48
184
78
401
543
682
3.00
42
40
55
197
81
437
574
750
3.25
47
45
64
209
84
466
605
819
3.50
53
51
73
223
87
488
635
887
3.75
57
58
84
235
92
508
668
946
4.00
62
64
95
247
99
528
697
995
4.25
66
71
106
259
111
547
722
1025
4.50
70
77
116
271
124
569
745
1045
4.75
74
84
127
282
138
589
764
1064
5.00
77
90
137
294
150
610
780
1091
5.25
80
97
147
305
158
631
792
1131
5.50
82
104
157
317
164
650
802
1183
5.75
84
110
167
327
169
667
810
1231
6.00
85
115
177
338
175
682
817
1273
6.25
87
121
188
347
183
692
825
1303
6.50
88
125
197
355
194
700
833
1320
6.75
89
128
206
362
211
707
839
1332
7.00
89
131
213
368
233
716
846
1343
7.25
90
133
219
374
261
727
852
1356
7.50
91
134
223
379
292
740
858
1371
7.75
92
135
226
384
323
754
864
1384
8.00
93
136
229
390
349
767
872
1395
8.25
396
369
780
881
1400
8.50
403
382
791
892
1404
8.75
410
394
799
901
1412
9.00
415
408
802
908
1430
9.25
418
424
801
912
1457
9.50
419
444
798
915
1491
9.75
419
466
795
917
1526
10.00
419
489
796
922
1554
10.25
803
929
1567
10.50
813
939
1570
10.75
824
949
1568
11.00
834
960
1565
11.25
840
969
1565
11.50
842
976
1567
11.75
843
983
1571
12.00
843
989
1575
12.25
1578
12.50
1581
12.75
1584
13.00
1588
13.25
1592
13.50
1598
13.75
1605
14.00
1611
Valve is fully open
Inches
MM
GPM
(LPH)
2-1/2
DN 65
39 - 87
(9k - 20k)
3
DN 80
87 - 125
(20k - 28k)
4
DN 100
125 - 213
(28k - 48k)
5
DN 125
213 - 300
(48k - 68k)
6
DN 150
300 - 450
(68k - 102k)
8
DN 200
450 - 760
(102k - 173k)
10
DN 250
760 - 920
(173k - 209k)
12
DN 300
920 - 1500
(209k - 341k)
Nominal
Dimensions
Valve Size
Valve Selection Guide
Nominal Range of Flow
CIR
CUI
T
SETTER
14
Содержание Macon AB Series
Страница 38: ...This page left blank intentionally MANUAL 38 ...
Страница 48: ...STRAINERS This page left blank intentionally 48 ...
Страница 52: ...This page left blank intentionally SHUT OFF VALVES 52 ...
Страница 56: ...This page left blank intentionally UNIONS 56 ...
Страница 74: ...74 ...
Страница 122: ...122 ...
Страница 144: ...144 ...