At most 10 air curtain systems can be managed with one control panel
with the UBT2-E control.
Each printed circuit board is equipped with a coding switch for this purpose.
The coding reads as follows:
0= MASTER, 1 - 9 = SLAVE.
NOTE: never use the same coding for two systems.
If input does not follow in the programming mode (
PRG Mode) for more than 60 seconds, the mode will be
terminated automatically.
Temperature sensor
The cable must be laid separately and must be as short as possible
DWPRVWPWRHQVXUHWKDWWKHVHQVRULVLQÁXHQFHGDVOLWWOHDVSRVVLEOH
by electromagnetic radiation.
The sensor cable must be shielded in unfavourable situations or when
the cable lengths are different (at most 20 m).
Room temperature sensor (dimensions 70 x 70 x 27 mm)
11. Messages
&OHDQÀOWHU
(QGRIDGMXVWHGÀOWHUOLIHWLPH&OHDQÀOWHUXUJHQWO\
Filter can cleaned by a vac cleaner or can wipped clean.
1RWH$IWHUDZHWFOHDQLQJRIÀOWHUGRUHSODFHÀOWHU
after complete drying of this!
5HVHWPHVVDJHV
Push MODE button (display PGM mode). By whipping
the multi funktional wheel select the prompt (text
FRORUFKDQJHVIURPRUDQJHWREODFNDQGFRQÀUPE\
pushing.
No enable
No enable by on-site BMS. The unit cannot start.
5HVHWPHVVDJHV
Automatically after setting a enable signal by BMS.
6HQVRUGHIHNW
and actual temperature display 01°C Temperature sensor broken, not connected or max.
wire length is exceeded.
6HQVRUGHIHNW
and actual temperature display 55°C Circuit short of tempearture sensor.
5HVHWPHVVDJHV
The message will be deleted if failure of temperature
sensor is removed, and the air curtain unit goes into
normal operation.