When the password entered correctly, press “SET” twice to enter the Port interface
then press “
→
” for three times to enter address page, and press “SET” button once to
start to set meter address.
⑤
Pressing “
→
” button to adjust the value of address, one increment per button
pressing.
⑥
After the address set successfully, press “ESC” button twice to exit to Measure
display interface to get the meter work.
5.7 External AC Circuit Breaker and Residual Current Device
Please install a circuit breaker to ensure the inverter is able to disconnect from grid
safely. The inverter is integrated with a RCMU, however, an external RCD is needed to
protect the system from tripping, either type A or type B RCD are compatible with the
inverter.
The integrated leakage current detector of inverter is able to detect the real time external
current leakage. When a leakage current detected exceeds the limitation, the inverter will
be disconnected from grid quickly, if an external residual current device is connected, the
action current should be 30mA or higher.