background image

 

 

5.  Installation  

1. Environmental specifications 

Install the Shock Relay in the following environment.  

  Temperature: 

20 to 

60

 not in direct sunlight.  

  Humidity

 45

85% relative humidity without condensation and freezing. 

  Place

 Indoors, no water splash.  

  Atmosphere

 Free from dust, corrosion gas, and oil mist. 

  Height:  2000m or less above sea level. 

 

Vibration:  5.9m/s

2

 and under. 

 

2. Installation to the panel 

Put the Attachment for installation at the both side or Shock Relay, and install 
Shock  Relay to the panel 

 

 

 

 

 

 

 

 

 

 

3. Installation to the DIN rail 

While pulling the hook of Shock Relay to the arrow direction, install Shock Relay 
to 35mm DIN rail. When removal, put the hook to the arrow direction with 
flathead screwdriver. 

 

6.  Wiring 

(1) Connect 100

240VAC power source to the terminal L1- L2. 

Never connect the output of an inverter or a servo driver to terminals L1-L2.  
Install an insulation transformer between the power line and terminals L1-L2 of 
the SHOCK RELAY when harmonic noise is included in the power line. 

(2) Check and correct the following items before turning the power on. 

a. Is there any misconnection? 
b. Have you forgotten to complete any connections? 
c. Are there any abnormal conditions such as a short-circuit or ground fault? 

 

       

       

       

       

WARNING

 

ELECTRICAL SHOCK AND BURN

 

Do not operate without the ground wire connected.

 

 

7.  Terminal Function 

Terminal 

Function

.  

Contents.  

L1 
L2 

Power  

Supply 

100 – 240VAC commercial power supply is wired 

95 

Common 

96 

Normally close

  (Power on : open   Power off or tripped: close) 

98 

Output 
Relay 

Normally open

  (Power on : close   Power off or tripped: open) 

 

Pull a hook in the direction of the arrow with a screwdriver to 
 remove the bracket.  

Mounting hole 

hook 

    

!!!!    

 

63 

2-M4 

Attachment 

 

L1

   

   

   

   

 

  

 

   

   

   

   

L2

   

   

   

   

       

       

       

       

95

     

     

     

     

96

   

   

   

   

         

         

         

         

98 

Содержание TSB2CT100

Страница 1: ...3 Edition When revisions of these standards are published the updated edition shall apply 6 Guards must be provided on all power transmission and conveyor applications in accordance with provisions of...

Страница 2: ...n to adjustment Be sure to read this manual carefully before using your Shock Relay When delivering a device containing the Shock Relay be sure that this instruction manual is included 2 TSBSS and TSB...

Страница 3: ...2 3 Dimensions Shock relay 72 61 Attachment Cover Screw Unit mm 1inch 25 4 mm...

Страница 4: ...3 External 2 phase CT Details for installation holes...

Страница 5: ...V 60Hz 1min Between contacts AC 1000V 60Hz 1min Dielectric Strength Between circuits and contacts AC 2000V 60Hz 1min Protection Structure IP20 115VAC 2 7 VA 0 35W Power Consumption 230VAC 11 0 VA 1 2W...

Страница 6: ...r source to the terminal L1 L2 Never connect the output of an inverter or a servo driver to terminals L1 L2 Install an insulation transformer between the power line and terminals L1 L2 of the SHOCK RE...

Страница 7: ...SBSS05 1 3 7 5 TSBSS30 3 7 5 TSBSS30 3 5 5 7 1 2 TSBSS30 1 5 5 7 1 2 TSBSS30 2 7 5 10 TSBSS60 1 7 5 10 TSBSS30 11 15 TSBSS60 1 11 15 TSBSS30 1 15 20 TSBSS60 1 18 5 25 TSBSS60 1 22 30 TSBSS60 1 Basic w...

Страница 8: ...urrent 100A 200A 300A Ratedsecondarycurrent 5A Ratedburden 5VA Ratedfrequency 50 60Hz Approximatelyweight 0 5kg Installation Procedure 1 Install the SHOCK RELAY on the External CT with screws accordin...

Страница 9: ...nd correct the cause Release the tripped Shock Relay by pressing the RESET button or by shutting power down before restarting the equipment As a fail safe the Shock Relay keeps the built in output rel...

Страница 10: ...ime 12 Troubleshooting Trouble Check Result Solution Wiring of the power source L1 L2 Not attached correctly Wire properly Even when the Shock Relay trips the 95 98 contacts do not shut down the attac...

Страница 11: ...dangerous situation from arising 16 Warranty Range of warranty With regard to any troubles happened to our products replacement or repair of such troubled parts will be provided for free of charge du...

Страница 12: ......

Отзывы: