4.  Specifications 

Series

 

TSB SS

 

Model 

Range 

05 

0.5-6A 

30 

3-30A 

Current Setting 

*

1

 

60 

5-60A 

Starting Trip Delay  Start Time 

0.2-30s 

Time Setting 

*

1

 

Trip Time 

Shock Time  0.2-10s 

Accuracy 

Current 

±10

 (Full scale ) 

Control Power Supply 

100

240VAC

±

10%, 50/60Hz   

Maximum motor voltage 

600VAC, 50/60Hz 

*

2

 

Current Sensing method 

2 Integral Current Transformer 

Mode 

1-SPDT(1c) 

Contact Rating (max.) 

3A / 240VAC  cos

φ

=1 

Contact Rating (min.)

  *

3

 

10VDC  10mA 

Operation 

Fail safe operation,Normally energized 

Reset 

Manual or Electrical (Interrupt power supply) 

Output Relay 

Expected Life 

100,000 operations 

Operating 

-20 - +60

 (-4 - +158 F) 

Temperature 

Storage 

-30 - +70

 (-22 - +176 F) 

Humidity 

45 – 85

 RH without Condensation 

Altitude 

2,000m max. 

Pollution degree 

Class 3 
To be free from dust and corrosive gas 

Ambient 
Environment 

Vibration 

5.9 m/s

2

 or less. 

Insulation 

Between casing and circuit 

Over 10M

Ω

with 500 VDC Megger 

Between casing and circuit 

AC 2000V,  60Hz,  1min 

Between contacts 

AC 1000V,  60Hz,  1min 

Dielectric Strength 

Between circuits and contacts 

AC 2000V,  60Hz,  1min 

Protection Structure 

IP20 

115VAC 

2.7 VA(0.35W) 

Power Consumption 

230VAC 

11.0 VA(1.2W) 

Case 

Polyamide 66 (PA66) 

Material 

Terminal cover 

Polyamide 6   (PA6) 

Mounting 

35mm DIN rail or Panel 

Dimension(W x H x D /Including Integral CT Windows) 

54 x 72 x 64.5 mm 

Weight 

Less than 200g (0.44LBS) without External CT 

*1  Current and time setting ranges can be set within the warranty range, but not the upper or lower 

level of setting volume. 

*2  When Shock Relay is used with Inverter, the output frequency of Inverter should be from 30Hz  
      to 60Hz. 

*3

 

When directly inputting output relay contact into the programmable controller (PLC), be aware 

that a minute electric current can cause contact failure

.

 

As for the input to PLC, it is commended 

to drive the relay coil for minute current by relay signal of Shock Relay at first, then input this 
relay contact to PLC. 

*4  CE marking 

   

 EMC Directive 03.05.1989    Low Voltage Directive 19.02.1973 

        EN60947-1  2001  EN50081-2  1993   EN55011 1991 
        EN50082-2  1995   EN61000-4-2  2002  ( 4kV) 

Содержание TSB2CT100

Страница 1: ...3 Edition When revisions of these standards are published the updated edition shall apply 6 Guards must be provided on all power transmission and conveyor applications in accordance with provisions of...

Страница 2: ...n to adjustment Be sure to read this manual carefully before using your Shock Relay When delivering a device containing the Shock Relay be sure that this instruction manual is included 2 TSBSS and TSB...

Страница 3: ...2 3 Dimensions Shock relay 72 61 Attachment Cover Screw Unit mm 1inch 25 4 mm...

Страница 4: ...3 External 2 phase CT Details for installation holes...

Страница 5: ...V 60Hz 1min Between contacts AC 1000V 60Hz 1min Dielectric Strength Between circuits and contacts AC 2000V 60Hz 1min Protection Structure IP20 115VAC 2 7 VA 0 35W Power Consumption 230VAC 11 0 VA 1 2W...

Страница 6: ...r source to the terminal L1 L2 Never connect the output of an inverter or a servo driver to terminals L1 L2 Install an insulation transformer between the power line and terminals L1 L2 of the SHOCK RE...

Страница 7: ...SBSS05 1 3 7 5 TSBSS30 3 7 5 TSBSS30 3 5 5 7 1 2 TSBSS30 1 5 5 7 1 2 TSBSS30 2 7 5 10 TSBSS60 1 7 5 10 TSBSS30 11 15 TSBSS60 1 11 15 TSBSS30 1 15 20 TSBSS60 1 18 5 25 TSBSS60 1 22 30 TSBSS60 1 Basic w...

Страница 8: ...urrent 100A 200A 300A Ratedsecondarycurrent 5A Ratedburden 5VA Ratedfrequency 50 60Hz Approximatelyweight 0 5kg Installation Procedure 1 Install the SHOCK RELAY on the External CT with screws accordin...

Страница 9: ...nd correct the cause Release the tripped Shock Relay by pressing the RESET button or by shutting power down before restarting the equipment As a fail safe the Shock Relay keeps the built in output rel...

Страница 10: ...ime 12 Troubleshooting Trouble Check Result Solution Wiring of the power source L1 L2 Not attached correctly Wire properly Even when the Shock Relay trips the 95 98 contacts do not shut down the attac...

Страница 11: ...dangerous situation from arising 16 Warranty Range of warranty With regard to any troubles happened to our products replacement or repair of such troubled parts will be provided for free of charge du...

Страница 12: ......

Отзывы: