Leakage Testing Standards Highlights
27
Should one of these conditions not be satisfied, then correcting
the leakage to standard conditions may be done using one of these
formulas:
1.
ACFM=SCFM * (460+T)/530
where T = actual dry bulb air temperature (ºF)
moisture is negligible
pressure between -20 and +20 inwg
2.
ACFM = SCFM * 0.075/d
where d = air density from psychrometric chart
3.
ACFM=lb dry air/minute * humid volume (ft
3
/lb dry air)
The SMACNA standard does not specify the information to be
reported, but instead defers to project documents. However, the
SMACNA standard does include a sample test report that
includes:
o
Test date and place
o
Test personnel and witness
o
Building and project reference
o
Duct section tested
o
Specified leakage class, test pressure and duct construction
pressure class
o
Measurements of:
Ductwork surface area
Leakage flow and calculations required to determine
leakage flow
www.netzerotools.com
www.netzerotools.com
Содержание PANDA PAN200 Series
Страница 4: ...iv This page intentionally left blank www netzerotools com www netzerotools com ...
Страница 8: ...4 Chapter 1 This page intentionally left blank www netzerotools com www netzerotools com ...
Страница 14: ...10 Chapter 2 This page intentionally left blank www netzerotools com www netzerotools com ...
Страница 24: ...20 Appendix A This page intentionally left blank www netzerotools com www netzerotools com ...
Страница 32: ...28 Appendix B This page intentionally left blank www netzerotools com www netzerotools com ...
Страница 33: ...29 Appendix C Typical Setup www netzerotools com www netzerotools com ...
Страница 34: ...30 Appendix C This page intentionally left blank www netzerotools com www netzerotools com ...
Страница 36: ...32 Appendix D This page intentionally left blank www netzerotools com www netzerotools com ...