Pressure Sensor Installation 

 

Figure 2:  Pressure Sensor Orientation and Mounting Template 

 

WARNING:  

800243 pressure sensor 

must

 

be mounted through the wall between the 
controlled space (isolation room) and 
referenced space (hallway), exactly as shown 
in Figure 2 and 3.

 

1.

 

Determine pressure sensor location 
(Figures 1, 2 and 3). Pressure sensor 
typically mounts in the reference space, 

and the dummy housing mounts in the 
isolation room. 

Note:

  Pressure sensor is not symmetrical. 

If sensor is to be centered over 
hallway door, measure one inch to 
the left of center for 2¼“ hole. 
Dummy sensor will be 2” off center 
on other side of wall. 

2.

 

The pressure sensor must be orientated 
on the wall as shown in Figure 2. 
Looking at the mounted sensor, sensor 
hole is on the left (2¼”) and wire hole is 
on the right. 

3.

 

Drill a 2¼-inch hole through each side of 
the wall to accept the sensor tube. 

4.

 

Drill a 7/8-inch hole on the side of the 

wall that the pressure sensor will be 
mounted. This hole is for the six-
conductor sensor cable. Refer to Figure 2 
for a hole mounting pattern. 

5.

 

Slide sensor cover to right and remove 
screw that holds the sensor base to the 
pressure sensor (Figure 2). Remove 
pressure sensor and store in a safe place. 

Содержание PRESSURA 8630

Страница 1: ...ed space ante room hallway These installation instructions guide the installer through the installation of the TSI Model 8630 PresSura Room Pressure Monitor Please read these instructions thoroughly before beginning installation This product is classified by Underwriters Laboratories Inc for use in through penetration firestop systems See UL fire resistance directory Figure 1 Typical Installation ...

Страница 2: ... hallway door measure one inch to the left of center for 2 hole Dummy sensor will be 2 off center on other side of wall 2 The pressure sensor must be orientated on the wall as shown in Figure 2 Looking at the mounted sensor sensor hole is on the left 2 and wire hole is on the right 3 Drill a 2 inch hole through each side of the wall to accept the sensor tube 4 Drill a 7 8 inch hole on the side of ...

Страница 3: ...er the end of the tube Screw the pressure sensor base and dummy base to the wall Figure 3 8 Wire the pressure sensor per Figure 7 Run sensor cable to the room pressure monitor 4 x 4 electrical rough in box 9 Insert fire protection sealant provided into 7 8 wire hole to seal 10 Install and screw the pressure sensor and dummy cover onto the bases Slide covers to the left to hide the sensor Finished ...

Страница 4: ...ox at a convenient location within 20 feet of pressure monitor 2 Run 115 Volt single phase 60 hertz line voltage 115 VAC to electrical box Follow all applicable electrical codes 3 Connect 115 VAC line voltage HOT wire to BLACK wire on transformer and NEUTRAL wire to WHITE wire on transformer Figure 5 4 Connect the RED wire on 800414 transformer cable to either of the YELLOW wires on the transforme...

Страница 5: ...crews are hidden behind the cover when full open The cover will slide to the right approximately 2 inches until a stop is hit Pull cover to completely remove from electronics and expose the screws Pressure Monitor Wiring WARNING Do not connect more than 24 VAC to any terminal Do not apply voltage to the RS 485 output analog output or control output Severe damage may occur to the unit if voltage is...

Страница 6: ...1 523030 India Tel 91 80 67877200 China Tel 86 10 8219 7688 Singapore Tel 65 6595 6388 P N 1980244 Rev F 2017 TSI Incorporated Printed in U S A WARNING Monitor must be wired exactly as wire diagram shows Making modifications to the wiring may severely damage the unit Figure 7 Wiring Diagram If you need assistance installing the system call TSI at 800 874 2811 ...