MODEL 8630 PRESSURA

 

ROOM PRESSURE MONITOR 

 

INSTALLATION INSTRUCTIONS 

 
 

WARNING:

 

The Model 8630 Room Pressure Monitor must be wired to 24 VAC only. Wiring the unit to 
110 VAC will cause serious damage to the unit and void the warranty. 
 
The pressure sensor must be mounted through the wall between the controlled space (isolation 
room) and referenced space (ante room / hallway). 

 

 

These installation instructions guide the installer through the installation of the TSI Model 8630 PresSura

 

Room Pressure Monitor. Please read these instructions thoroughly before beginning installation.  

 

 

This product is classified by Underwriters Laboratories, Inc.

®

 for use in through-penetration 

firestop systems. See UL fire resistance directory. 

 

 

Figure 1: Typical Installation  

Component List 

 

Part Number 

Qty 

Description 

800243 

Pressure sensor 

800248 

Sensor cable 

800244 

8630-SM Room pressure 

monitor 

 

or 

800245 

8630-PM Room pressure 

monitor 

800420 

Transformer 

800414 

Transformer cable 

1901057 

Intumescent ring 

2923020 

Fire sealant

 

 

 

Содержание PRESSURA 8630

Страница 1: ...ed space ante room hallway These installation instructions guide the installer through the installation of the TSI Model 8630 PresSura Room Pressure Monitor Please read these instructions thoroughly before beginning installation This product is classified by Underwriters Laboratories Inc for use in through penetration firestop systems See UL fire resistance directory Figure 1 Typical Installation ...

Страница 2: ... hallway door measure one inch to the left of center for 2 hole Dummy sensor will be 2 off center on other side of wall 2 The pressure sensor must be orientated on the wall as shown in Figure 2 Looking at the mounted sensor sensor hole is on the left 2 and wire hole is on the right 3 Drill a 2 inch hole through each side of the wall to accept the sensor tube 4 Drill a 7 8 inch hole on the side of ...

Страница 3: ...er the end of the tube Screw the pressure sensor base and dummy base to the wall Figure 3 8 Wire the pressure sensor per Figure 7 Run sensor cable to the room pressure monitor 4 x 4 electrical rough in box 9 Insert fire protection sealant provided into 7 8 wire hole to seal 10 Install and screw the pressure sensor and dummy cover onto the bases Slide covers to the left to hide the sensor Finished ...

Страница 4: ...ox at a convenient location within 20 feet of pressure monitor 2 Run 115 Volt single phase 60 hertz line voltage 115 VAC to electrical box Follow all applicable electrical codes 3 Connect 115 VAC line voltage HOT wire to BLACK wire on transformer and NEUTRAL wire to WHITE wire on transformer Figure 5 4 Connect the RED wire on 800414 transformer cable to either of the YELLOW wires on the transforme...

Страница 5: ...crews are hidden behind the cover when full open The cover will slide to the right approximately 2 inches until a stop is hit Pull cover to completely remove from electronics and expose the screws Pressure Monitor Wiring WARNING Do not connect more than 24 VAC to any terminal Do not apply voltage to the RS 485 output analog output or control output Severe damage may occur to the unit if voltage is...

Страница 6: ...1 523030 India Tel 91 80 67877200 China Tel 86 10 8219 7688 Singapore Tel 65 6595 6388 P N 1980244 Rev F 2017 TSI Incorporated Printed in U S A WARNING Monitor must be wired exactly as wire diagram shows Making modifications to the wiring may severely damage the unit Figure 7 Wiring Diagram If you need assistance installing the system call TSI at 800 874 2811 ...

Отзывы: