7

Trouble-shooting list 

Flash code on the control panel
Flash sequence LED:
– On: 

0.5 seconds

– Off: 

0.5 seconds

Pause between the flashing sequence: 3 seconds

 

 Fault

   Cause

   Rectification

After switching on 
(winter and summer opera-
tion) none of the LEDs are lit.

–  No operating voltage.

–  Device fuse or vehicle fuse 

defective.

 

–  Check 12 V battery voltage, charge if necessary.

–  Check all electrical plug connections.

–  Check the unit or vehicle fuse and replace if necessary 

(see fuses).

The green LED comes on 
when the unit is switched 
on, but the heater does not 
operate.

–  The temperature  setting 

on the control panel is 
lower than the room 
temperature.

–  Select higher room temperature at the control panel.

Green LED flashes after 
heater is switched off.

–  After-running is active in 

order to reduce the unit’s 
temperature.

 – No error. Coasting operation switches off after 

max. 5 minutes. 

Red LED flashes 6 x.

–  Insufficient fuel due to 

insufficient fuelling, empty 
tank, and / or inclined 
 vehicle orientation.

–  Fill tank with fuel. Then fill the fuel line as described under 

“Initial start-up”.

Red LED flashes (except 
6 times) or red LED shines.

–  Malfunction of the heating 

device.

–  Please contact the Dometic Service.

Yellow LED flashes 1 x.

–  Possible under-voltage 

< 11.5 V.

–  Use the electrical power from the battery carefully, 

e.g. restrict lighting.

– Charge battery.

Yellow LED flashes 2 x.

–  Under-voltage < 10.2 V.

–  Check battery voltage, charge if necessary.

–  Short-term immediate measure: switch off heavy load 

or start up vehicle engine until the heater starts running 
 (approx. 4 minutes).

–  Battery capacity inadequate, if necessary exchange old 

battery.

–  Over-voltage > 15.8 V.

–  Check the battery voltage and power supply such as e.g. 

the charging device.

Yellow LED flashes 3 x.

Yellow LED flashes 4 x.

–  Open window above cowl 

(window switch).

–  Warm air temperature 

and / or water temperature 
exceeded:

  –  Not all warm air ducts 

are connected.

  –  Hot-air outlets blocked.

  –  Recirculated air intake 

blocked.

– Summer operation with 

empty water tank.

– Close window.

–  Check whether the 4 warm air ducts are connected.

–  Check individual outlet apertures.

–  Remove blockage from recirculated air intake.

–  Fill boiler with water.

Yellow LED flashes 5 x.

–  Room temperature sensor 

or cable defective.

–  Please contact the Dometic

 

Service.

Yellow LED flashes 7 x.

–  Control panel or control 

panel cable defective.

–  Please contact the Dometic

 

Service.

Содержание Combi 6

Страница 1: ...Comfort on the move 1 3 5 7 9 60 Combi 1 2 3 4 5 60 Combi D 6 Australia Operating instructions Page 2 To be kept in the vehicle...

Страница 2: ...mperature dif ference between the temperature set on the control panel and the current room temperature When the boiler is filled the water is automatically heated as well The water tem perature depen...

Страница 3: ...placed near or directly beneath an open ing window the device must be equipped with an automatic shut off device in order to prevent operation with the window open The exhaust gas double duct exhaust...

Страница 4: ...heater normally has to be started up several times to fill the fuel lines Connect unit to control panel to do this The unit automatically performs 2 start attempts initial start and repeat per switch...

Страница 5: ...heck that the drain valve in the cold water intake is closed Lever should be in horizontal position position k m k k k Lever position Closed m Lever position Drain Switch on the power for the water pu...

Страница 6: ...els 2000 4000 6000 W Fuel consumption 220 630 ml h in regular operation between Off and lowest operating level less than 190 ml h Air delivery volume free blowing without hot air pipe max 287 m h Curr...

Страница 7: ...hes except 6 times or red LED shines Malfunction of the heating device Please contact the Dometic Service Yellow LED flashes 1 x Possible under voltage 11 5 V Use the electrical power from the battery...

Страница 8: ...ction of safety drain valve Water pressure too high Check pump pressure max 400 kPa If connected to a central water supply rural or urban connection a pressure reducer must be used which will prevent...

Страница 9: ...warranty you should contact Dometic Pty Ltd Whilst this book represents service outlets at the time of printing changes occur from time to time Should you have any queries or wish to locate your neare...

Страница 10: ......

Страница 11: ...Combi D 6 Australia...

Страница 12: ...ommer ant Timbro del rivenditore Dealeradres Forhandleradresse Direcci n del comerciante In Australia always notify the Dometic Service Centre if problems are encountered in other countries the releva...

Отзывы: