ELSTAT SEQUENCE OF OPERATION

Once the cabinet is plugged in, the ELSTAT control will flash "888" and then 
go through a parameter check. Once completed, the control will do a "soft 
start". Lights come on first, approximately 30 seconds later the compressor 
will start. Approximately 30 seconds from the compressor start up, the evap 
motor will start. The control will display "Use".  The control will then cycle 
the compressor on and off at the predetermined temp (Model specific). 

The whole time the controller is on it is learning the customer traffic. Once 
enough data has been accumulated the controller will now cycle between 
two modes. "Standby" and "Use". In the standby mode the controller 
predicts that customer traffic is nonexistent. It will display (---). It cycles the 
compressor to hold about 50˚F. It shuts the lights off and cycles the evap 
fan motor. It will hold this pattern until roughly 2 hours before customer 
traffic is predicted to start. The controller will then switch into the "use" 
mode. Cycling the compressor on and off based on temperature (Approx 
36˚F to 38˚F product temp). Running lights continuously. The controller will 
then cycle between these two modes.

   3

Содержание GDM-26

Страница 1: ...ELSTAT TRAINING BOOKLET GDM SERIES COOLER EQUIPPED WITH EMS ELSTAT CONTROL GDM 26...

Страница 2: ...CONTENTS ELSTAT SEQUENCE OF OPERATION ELSTAT COMPONENTS FRONT VIEW OF ELSTAT REAR VIEW OF CONTROLLER FREQUENTLY ASKED QUESTIONS FAQ NORMAL OPERATING CODES FAULT CODES TROUBLESHOOTING TROUBLESHOOTING...

Страница 3: ...me the controller is on it is learning the customer traffic Once enough data has been accumulated the controller will now cycle between two modes Standby and Use In the standby mode the controller pre...

Страница 4: ...porator fan motor Probe Location 1 GDM 45 to GDM 72 Probe is in the discharge air stream Off of the Evaporator Coil GDM SERIES COOLER EQUIPPED WITH EMS ELSTAT CONTROL ELSTAT COMPONENTS Probe Transform...

Страница 5: ...ra Lane O Fallon MO 63366 ph 636 240 2400 toll free 800 325 6152 service truemfg com GDM SERIES COOLER EQUIPPED WITH EMS ELSTAT CONTROL FRONTVIEW OF ELSTAT Waterdrops Snowflake Up Down Key Perishable...

Страница 6: ...2400 toll free 800 325 6152 service truemfg com NO NAME 1 Line In 2 Lights 3 Not Used 4 Appliance Sensor 5 Compressor 6 Fan s 7 12 Vac 8 Not Used 9 Not Used GDM SERIES COOLER EQUIPPED WITH EMS ELSTAT...

Страница 7: ...o enter the key dance Press the snow flake key 3 beeps Press the up arrow key 2 beeps Press the down arrow key1 beep Press the water drops key 4 beeps should show display of PS Now press and hold down...

Страница 8: ...Probe Ohm out evaporator probe Faulty Controller Bypass control to see if system will run Parameters have been changed Check the parameter list Power supply voltage is low Possible Problems Action to...

Страница 9: ...de 2 Move cabinet or put into Perishable mode 3 Unit was in a previous location 3 Perform half reset Warm Product 1 Unit in a unpredictable location Elstat control may be going into standby mode 1 Mov...

Страница 10: ...JY 2 2013 2001 East Terra Lane O Fallon MO 63366 ph 636 240 2400 toll free 800 325 6152 service truemfg com...

Отзывы: