Installation
1.5 D
VFC
VFC
Manifold
Installation in a branch
Connection with ducting
Installation behind a bend
Combination with volume flow rate measuring unit
VFC
Suspension
D
min. 1 D
Connection
elements, e.g.
tube clamp with
rubber seal
Installation location and type of connection
• Select the installation location so the scale and
characteristic of the controller remain accessible.
•
With reference to the characteristic, set the pointer to the
required volume flow rate.
• Horizontal or vertical controller installation.
•
Note the airflow direction according to the arrow on the
characteristic.
•
Note for installation in front of and behind elbows, flaps
or other obstacles with aerodynamic and acoustic effects.
•
Horizontal or vertical installation; in combination with
volume flow rate measuring unit (VMR), arrange the sensor
tubes at 45° offset from the controller axis.
•
Installation behind a bend:
Maintain a curvature radius of at least 1D unless there
is an additional straight inflow length.
•
Direct connection to a main duct/manifold: Maintain at least
1.5 D straight inflow length
•
Shorter inflow lengths result in tighter tolerances.
•
Direct connection to a main duct is permitted without
perforated sheet metal in extract air operation.
•
Free intake not permitted, inflow length 1.5 D required.
Inflow nozzles are recommended in order to reduce the
pressure losses.
Connection with ducting
The connection diameters are appropriate for tubes
according to EN 1506 or EN 13180.
•
No drilling work is allowed to be performed on the
controller!
•
Before connecting the controllers, check the ducting
for contamination.
• Use standard TROX lip seals for connecting to the ducting.
VMR