6
Operating manual
TROX air terminal units
Type VFC volume flow controllers
Actuator E01 ... E03
Setting the set flow rate
Each VFC carries a characteristic to determine the setting
values on site (see example, nominal size 160).
min
values below 3 results in an unregulated airflow dependent
on the duct pressure that is not less than
min-unit
.
Set the set flow rate as follows:
•
Determine the setting value for the set flow rate from the
characteristic or the table on page 5.
• Set the values on the
min
-
and
max
potentiometers.
•
Factory setting:
min
= 4
max
= 8
•
Shut-off down to leakage airflow is possible, value to be set 0
Functional test
A functional test can be performed very easily using the service
button and the indicator light.
• Press service button for at least 1 second
•
Actuator turns toward
min
•
Actuator turns toward
max
• Actuator returns to control mode
Indicator light provides functional information
•
Permanently on
: Position set
•
Flashing once a second : Actuator operating
•
Flashing twice a second : Actuator is jammed and stationary
•
Off
: No supply voltage
Actuator E03
The relationships between the setting value and output signal
U, or control signal w, are shown in the two characteristics on
the left.
The output signal does not correspond to the currently
measured volume flow rate, but reflects the setpoint value.
Example:
Factory set values:
min
= 4
min
= 8
Required value: 6
--> Required control signal: 5 V
Available output signal: 6 V corresponding to set value 6
max
potentiometer
Indicator light
Service button
min
potentiometer
Variable volume flow rate operation, actuator with
potentiometers
Characteristic for determining the volume flow rate
0
6
10
0
6 V
10 VDC
0
6
4
8
10
max
min
0
5 V
10 VDC
Characteristic of the actual value signal
Characteristics of the control signal
Output signal U
Control signal w
Value to be set
Value to be set
E03
E03
60
100
65
50
38
100
150
200
250
300
350
392
VFC 160
18
40
80
120
140
185
160
180
100
200
300
400
500
550
450
350
250
150
666
600 650
3
4
5
6
7
8
9
10
l/s
cfm
m³/h