Inspection and Maintenance

7

Function Test

Smoke detectors must be inspected every 3 months after
commissioning of the air conditioning system and
maintenance carried out at yearly intervals. Inspection 
and maintenance can be carried out at the same time.

Inspection

Pressing the “Test/Reset” button on the smoke detector 
or on the remote control terminal interrupts the circuit to 
the control device on the fire damper which then closes. 
On releasing the button, fire dampers with actuators
automatically return to the open position. Fire dampers 
with solenoid or magnet release must be opened locally 
by hand.
The fouling of the smoke alarm can be scanned directly on
the smoke detector using the diagnostic instrument and/or
via the remote control terminal.

For signal indication, see overview of functions, page 6.

Maintenance

Check the following:
– Application and installation position 

(during commissioning and after system changes)

– Correct electrical connections and no loose wires in 

terminals

– Electrical interaction of signal emitter, display and control

devices on fire damper

– Response of smoke alarm to smoke aerosol, e.g. cigarette

smoke or smoke from smoke cartridge. When the
permitted concentration limit is exceeded, the smoke
alarm interrupts the circuit to the control device on the 
fire damper to be controlled and the damper closes

– Check response of air velocity monitor, e.g. switch off fan

For signal indication see overview of function, page 6.

Eliminating Faults

If inspection or maintenance has revealed any faults, these
must be repaired immediately. Faulty components must be
replaced only by original Trox spare parts.

Only the manufacturer may make repairs to the smoke
detector.

If a function test reveals that the smoke detector is working
correctly but the fire damper to be controlled is not closing,
the control device on the damper and the damper itself
must be checked for operation.

Smoke detector with power supply, monitoring electronics,
smoke alarm and air velocity monitor

Connection (plug socket) for diagnostic instrument

Pushbutton “Test/Reset”

Green LED “System Monitoring”

Red LED “Alarm”

Yellow LED “Pollution Monitoring”

Blue LED “Air Velocity Monitoring”

 

Air duct supplied by others

Test tube for checking
response/function 
(by others)

13

1

2

3

4

5

6

7

Approx. 80-90

20

Approx. 90-100

Содержание RM-O-VS

Страница 1: ...Smoke Detector Type RM O VS Approved by the German Institut f r Bautechnik 4 6 1 EN 3...

Страница 2: ...y condensation and water vapour can cause false alarms Warning limit for air flow 2 m s Warning limit for high pollution 70 10 units System monitoring electric fault EMC interference suppression to EN...

Страница 3: ...by an LED and closing relay contact The actual pollution value can be scanned directly at the smoke detector or on the remote control terminal using the diagnostic instrument Installation of a remote...

Страница 4: ...r to replace the smoke alarm an inspection opening should be provided on the upper or lower side of the air duct Optional electrical connections mains connection and connection to control device of fi...

Страница 5: ...trol device A on the fire damper to be controlled maximum switched power 250 V 10 A L1 Mains connection 230V 50 60 Hz L3 Control device connection volt free Switched power 250 V 10 A or 24 V 200 W L4...

Страница 6: ...Velocity Monitoring Green LED System Monitoring Terminal Strip L9 6 5 Terminal Strip L9 4 3 Terminal Strip L9 2 1 Terminal Strip L3 2 3 1 Yellow LED Pollution Monitoring With air flow LED on Without a...

Страница 7: ...rol devices on fire damper Response of smoke alarm to smoke aerosol e g cigarette smoke or smoke from smoke cartridge When the permitted concentration limit is exceeded the smoke alarm interrupts the...

Страница 8: ...ution level on the smoke alarm sampling chamber and the system electronics maintenance once year Scope of supply see page 2 Order Example Make TROX Type RM O VS Quantity 5 RM O VS Order Code Descripti...

Отзывы: