Technical data
Technical data
Supply voltage
24 V AC ±15% 50-60 Hz
24 V DC ±15%
Do not use 24 V AC and 24 V DC power supplies at the same time!
Optional: 230 V AC mains supply, only with the EM-TRF expansion module; optional: 230 V AC
mains supply with UPS, only with the EM-TRF USV expansion module
Power rating
The maximum power required depends on the construction of the controller. Typical construc-
tions with different equipment result in the following values:
Fume cupboard controller with control panel
Room controller
Room controller with room control panel
Including all expansion modules
35 VA
29 VA
33 VA
40 VA max.
Connecting cable
Double-stack terminal blocks for cables with a cross section up to 2.5 mm²
The 24 V supply voltage may be connected for a maximum of 5 controllers.
Micro fuse
2.5 A, slow blow, 250 V, as glass fuse 5 x 20 mm
Volume flow rate
measurement
Differential pressure transducer with room air induction to protect the measurement point
Optional: Automatic zero point correction only with expansion module EM-AUTOZERO
Actuator
Fast-running high-precision actuator,
∡
90°: 3 s
Flow rate setting time
≤ 2 s, depending on duct pressure
Controller recovery
time after supply
voltage failure
< 500 ms
Plug and play commu-
nication system
With automatic detection of the connected equipment and equipment functions:
Communication cable: 300 m max.
Number of controllers: max. 24 per segment
Temperature range
Operation: 0 to +50 °C
Storage: -10 to +70 °C
Humidity
<90% no condensation
Area of application
Enclosed spaces
Protection level
IP20
IEC protection class
III (protective extra-low voltage)
Technical data
EASYLAB controller Serie TCU3
8
Содержание EASYLAB TCU3 Series
Страница 1: ...EASYLAB controller Serie TCU3 Installation and operating manual GB en...
Страница 27: ...Appendix EASYLAB controller Serie TCU3 27...
Страница 30: ...EASYLAB controller Serie TCU3 30...
Страница 31: ...EASYLAB controller Serie TCU3 31...
Страница 32: ...EASYLAB controller Serie TCU3 32...