Tube connection on the pressure transducer
Room pressure control – supply air
Measuring
point
Tube connection PT699
Positive
Room pressure
Negative
Room pressure
1
+
–
2
–
+
Room pressure control – extract air
Measuring
point
Tube connection PT699
Positive
Room pressure
Negative
Room pressure
1
+
–
2
–
+
7
Wiring
Safety instructions
Personnel:
Skilled qualified electrician
DANGER!
Danger of death due to electric current!
Danger of electric shock! Do not touch any live
components!
–
Switch off the supply voltage and secure it
against being switched on accidentally
before working on the unit.
–
Ensure that no voltage is present.
–
Work on the electrical system must only be
carried out by skilled qualified electricians.
CAUTION!
Risk of damage to the controller
For wiring please note:
–
Do not connect the 24 V supply if the EM-
TRF or EM-TRF-USV expansion module has
been installed.
–
Do not connect 230 V and 24 V supply vol-
tages at the same time.
–
Do not connect Terminals 1 + 2 with
Comm 1 + 2.
–
Never connect 24 V AC and 24 V DC supply
voltage at the same time.
–
Never connect the PC or Comm 1 + 2 to the
connection (Fig. 4/18 - Terminal 3).
Wiring
EASYLAB controller Serie TCU3
20