3.
Zero point correction of the diaphragm pres-
sure transducer is required as part of com-
missioning (not required for controllers with
expansion module EM-AUTOZERO).
The EasyConnect software recognises the
system configuration and guides you
through the required steps. Zero point cor-
rection: Remove the two measuring tubes
(blue and white) (1) from the angled
pieces (2) on the sensor tube or from the
T pieces (3) on the controller.
Zero point correction can alternatively
also be carried out with the EasyCon APP.
When the zero point correction is finished,
reconnect the measuring tubes.
Adaptation of the actuator (only for fast-running
actuator TUS)
4.
VAV terminal units with a TROX actuator
NMQ24A-SR TR (M466EQ0) have to be
adjusted as part of commissioning. This
ensures that any incorrect position, e.g. due
to shipping or installation, is corrected. To
adjust the actuator, press the green 'Adap-
tion' button. The status LED lights up
(orange) and the actuator is moved to its
end position. When adjustment is complete,
the status LED goes off.
Adaptation of the actuator (only for fast-running
actuator TROX TUSD)
5.
For air terminal units with TROX type HPD
actuator (A00000067751), adaptation must
be carried out during commissioning. This
ensures that any incorrect position, e.g. due
to shipping or installation, is corrected.
To do this, press the
‘diagnostics
è
push button Adaption’
in the EasyCon-
nect software.
Commissioning
EASYLAB controller Serie TCU3
23
Содержание EASYLAB TCU3 Series
Страница 1: ...EASYLAB controller Serie TCU3 Installation and operating manual GB en...
Страница 27: ...Appendix EASYLAB controller Serie TCU3 27...
Страница 30: ...EASYLAB controller Serie TCU3 30...
Страница 31: ...EASYLAB controller Serie TCU3 31...
Страница 32: ...EASYLAB controller Serie TCU3 32...