Fault description
Cause
Remedy
Personnel
Electrical noises
The clock frequency of
the frequency inverter is
too low
Increase the clock frequency
Skilled qualified
electrician
8.3 Commissioning once a fault has
been rectified
Once the fault has been rectified, work through the fol-
lowing steps for recommissioning:
1.
Reset the emergency stop equipment.
2.
Acknowledge the fault on the control.
3.
Ensure that nobody is in the hazardous area.
4.
Start in accordance with the information in the
chapter entitled “
Faults
Commissioning once a fault has been rectified
Centrifugal roof fans DRH; DRV; DRVF; DRVF-H; BVD; BVD(F600)
38