Fault description
Cause
Remedy
Personnel
Air volume flow rate
is incorrect
Open the bypass
Reduce pressure losses in the duct
Dampers or grilles in
the system are closed
Open the dampers or grilles
Instructed person
An object is obstructing
the airflow in the duct
Clean the duct / remove the obstruction
Instructed person
Vane controls are (parti-
ally) closed
Open the vane control
Instructed person
Filter is dirty
Clean or replace the filter
Instructed person
Fan is pumping
Fan is working in an
unfavourable character-
istic curve range
Reduce the system resistances.
Instructed person
Increased vibrations Impeller imbalance due
to deposits
Please note that the system, consisting of the
impeller and motor, always has a residual
imbalance, even if all of the components are
balanced!
Clean and rebalance the impeller
Instructed person
Vibration isolators are
assembled or posi-
tioned incorrectly
Incorrectly selected vibration isolators can
result in the destruction of the fan!
Construct and assemble vibration isolators
correctly
Instructed person
Vibration isolators are
the wrong size
Replace the vibration isolators
Instructed person
Air noises
Direction of rotation is
incorrect
Change the direction of rotation by switching
two live wires on the terminals
Skilled qualified
electrician
Pulsating volume flow
rate
Have the standard rules for the installation of
fans been observed?
Increase the cross sections to improve the
passage of air
Install baffle plates
Instructed person
Is the operating point in an unstable range?
Implement measures to reduce the overall
pressure loss
Instructed person
Mechanical noises
Contamination on the
casing or impeller
Clean the casing / impeller
Instructed person
Impeller is grinding
Caused by a misaligned connection duct due
to deformation of the casing, for example.
Check the impeller gap
Realign the fan
Readjust the impeller
Instructed person
Bearing noises
Some bearings make clicking noises that can
be disregarded!
Check the bearings and replace them if nec-
essary
Instructed person
Bearing running dry
Instructed person
Faults
List of faults
Centrifugal roof fans DRH; DRV; DRVF; DRVF-H; BVD; BVD(F600)
37
Содержание BVD F600
Страница 47: ...Appendix Appendix Centrifugal roof fans DRH DRV DRVF DRVF H BVD BVD F600 47...
Страница 61: ...Centrifugal roof fans DRH DRV DRVF DRVF H BVD BVD F600 61...
Страница 62: ...Centrifugal roof fans DRH DRV DRVF DRVF H BVD BVD F600 62...
Страница 63: ...Centrifugal roof fans DRH DRV DRVF DRVF H BVD BVD F600 63...