Fire dampers
FKR-EU
1
K4 – 1.1 – 34
Circular fire damper with or without flanges,
for the isolation of duct penetrations
between fire compartments.
Tested for fire resistance properties to EN 1366-2,
with CE marking and declaration of performance
according to
the Construction Products Regulation.
Ready-for-operation unit, which includes a fire-
resistant damper blade and a release mechanism.
For mortar-based installation into solid walls
and ceiling slabs and in combination with
wooden beam ceilings and modular ceilings
(Cadolto system) as well as into lightweight
partition walls with one-sided cladding
(shaft walls) with or without metal support
structure. For mortar-based installation and dry
mortarless installation into lightweight partition,
fire walls, safety partition walls and walls to
provide radiation protection with metal support
structure or steel substructure as well as timber
stud walls and half-timbered constructions
with cladding on both sides.
Casing length 495 mm or 550 mm,
for the connection to ducts made of non-
combustible or combustible materials.
Thermal or thermoelectric release at 72 °C
or 95 °C (warm air ventilation systems).
Constructions with spring return actuator for
opening and closing the fire damper independent
of the nominal size and even while the ventilation
system is running, e.g. for a functional test.
Explosion-proof constructions for zones 1, 2, 21
and 22 with limit switch or spring return actuator.
Special characteristics
– Declaration of performance according to
Construction Products Regulation
– Classification to EN 13501-3,
up to EI 120 (v
e
, h
o
, i ↔ o) S
– Building inspectorate licence Z-56.4212-991
for fire resistance properties
– Complies with the requirements of EN 15650
– Tested to EN 1366-2
for fire resistance properties
– Hygiene complies with VDI 6022
part 1 (07/ 2011), VDI 3803 (02/2010),
DIN 1946 part 4 (12/2008),
and EN 13779 (09/2007)
– Corrosion protection according to EN 15650
in connection with EN 60068-2-52
– Closed blade air leakage to EN 1751, class 4
– Casing air leakage to EN 1751, class C
– Low differential pressure
and sound power level
– Any airflow direction
– Integration into the central BMS
with TROXNETCOM
Materials and surfaces
Casing:
– Galvanised sheet steel
– Galvanised sheet steel,
powder-coated RAL 7001
– Stainless steel 1.4301
Damper blade:
– Special insulation material
– Special insulation material with impregnation
Other components:
– Damper blade shaft in stainless steel
– Plastic bearings
– Seals of elastomer
The construction variants with stainless steel
or powder-coated casing meet even more critical
requirements for corrosion protection.
Detailed listing on request.
Technical data
– Nominal sizes: 315 to 800 mm
– Casing lengths: 495 and 550 mm
– Volume flow rate range:
Up to 6000 l/s or 21600 m³/h
– Differential pressure: up to 2000 Pa
– Temperature range: –20 – 50 °C
– Release temperature 72 °C or 95 °C
(for use in warm air ventilation systems)
– Upstream velocity:
≤ 8 m/s with standard construction;
≤ 12 m/s with spring return actuator
Sizing data
–
______________________________ [m³/h]
– Δp
st
______________________________ [Pa]
– L
WA
Air-regenerated noise __________ [dB(A)]
Description
This specification text
describes the general
properties of the product.
Texts for variants can be
generated with our Easy
Product Finder design
programme.
03/2017 – DE/en