Accessories 1
I
nstallation kit – for installation in lightweight partition walls/fire walls
06/2015 – DE/en
FK-EU
1
/
ES
/
Order code detail
Application
– Installation without perimeter mortar infill
(dry mortarless installation) in lightweight
partition walls with metal support structure
and cladding on both sides, or installation
in shaft walls with or without metal support
structure but with cladding on one side
requires an installation kit.
– Fire damper and installation kit
are supplied unassembled
– Assembly and installation
are to be performed by others
– Fire dampers with installation kit
only with casing length L = 500 mm
– The fire damper and the installation kit
must be installed and secured according
to the operating and installation manual
Materials and surfaces
– Installation kit made from special insulation
material with intumescent seal and mineral
wool strips
– Fixing elements made of galvanised steel
Description
K 4 – 1.1 – 23
Installation kit for dry mortarless installation in lightweight partition walls,
fire walls and shaft walls
L [mm]
Order code
500
ES
FK-EU with installation kit ES
L = 500
~ 90
B + 95 /
H + 95
190
ݣ
ݢ
ݣ
ݣ
ݢ
ݣ
ݢ
ݢ
ݢ
ݤ
Installation kit ES, consisting of:
①
Installation kit
②
Fixing elements
③
Lightweight partition wall or fire wall
with metal support structure