Declaration of Performance

  

DoP-ERK-MB-2019-04-01 

 
 
 
 
 

 

 

CLASSIFICATION AND STANDARDS 

 

Classification 

according to EN 13501-4 is EI  90 (v

edw

, h

od

 

i↔o) S 1000 C

10000

 MA multi, depending on 

the mounting situation 

 

Product standard

 

EN 12101-8 

 

Test standards

 

EN 1366-2 and EN 1366-10 

 

 
 
 

PERFORMANCE DATA 

 

For ventilating smoke in smoke extraction sys-
tems and for providing the necessary supply air 
within the smoke extraction installation 

 

A wide range of installation situations: Suitable 
for use in partition walls (solid and dry building 
walls) and smoke extraction ducts. 

 

Space-saving installation: low installation depth 
of only 250 mm 

 

For automatic (AA) or manual (MA) triggering 

 

SPECIAL FEATURES 

 

Thermally insulated actuator housing, lateral or 
front operation 

 

The installation position does not depend on the 
air flow direction or the position of the blade 
damper axles 

 

Reversible OPEN/CLOSED actuator with  
24

 

V

 

AC

/

DC

 

or

 

230

 

V

 

AC

 

supply voltage 

 

Optional actuator with Powerline SLC bus tech-
nology possible. 

 

In conjunction with additional communication 
devices it is possible to retrieve further data, for 
example indication of end position, keeping 
timeframe (<60 s) or torque monitoring. 

ERK-MB

Smoke extraction blade damper 

TECHNICAL DOCUMENTATION 

with installation, mounting and operating in-

Содержание ERK-MB Series

Страница 1: ...ions Suitable for use in partition walls solid and dry building walls and smoke extraction ducts Space saving installation low installation depth of only 250 mm For automatic AA or manual MA triggerin...

Страница 2: ...he front side on or in horizontal smoke extraction ducts 15 Connection options on the side of the horizontal smoke extraction ducts in accordance with EN 12101 7 inspected according to EN 1366 8 16 Fr...

Страница 3: ...13669 The national standards and guidelines must be observed in connection with this technical documentation installation mounting and operating instructions For functional test service retrofitting e...

Страница 4: ...ncl inspection cover Operation ERK MB S For installation in vertical and horizontal smoke extraction ducts made of calcium silicate according to EN 12101 7 inspected according to EN 1366 8 on the fron...

Страница 5: ...length of the housing will be increased they are available upon request and at an extra charge Operating side inspection cover always on H side Number of blade dampers depends on the height H Other w...

Страница 6: ...wall in in dry building walls with metal posts and panelling on both sides according to classification to EN 13501 2 or comparable national standards 100 from one another 200 EI 90 vew i o S 1000 C100...

Страница 7: ...storage smoke extraction blade dampers must be pro tected from dust dirt moisture and the effects of extreme temperatures They must not be exposed to direct effects of the weat her o The smoke extract...

Страница 8: ...o EN 998 2 previously MG III ac cording to DIN 1053 or fire protection mortar of suitable grades The minimum gap size smin is 10 mm maximum gap size smax 50 mm The mortar lining must be executed such...

Страница 9: ...nal mounting kit type MS for connecting the smoke extraction blade dampers is requi red The connections must be made on site The distance to other ERK MB dampers is 200 mm these dampers may be install...

Страница 10: ...d mounting dimensions are observed Connection of the two smoke extraction blade dampers by me ans of 6 Hexagon screws with shaft similar to DIN 931 ISO 4014 M8 x 100 mm 7 U washers to DIN 125 ISO 7089...

Страница 11: ...note The screw heads do not need to be coun tersunk if the specified mounting dimensions are observed Detail Arrangement of the screw connection Bores 10 mm for screw connections 9 Insulfrax paper 5...

Страница 12: ...mm When installed on solid smoke extraction shafts in connection with mounting brackets WE S the distance between them is 200 mm and the distance to adjacent compo nents wall solid ceiling due to the...

Страница 13: ...s defined and carried out in factory according to the ERK MB V dimensions The brackets are mounted to solid smoke extraction shafts depending on the dimensions Information about it can be found in the...

Страница 14: ...osts in accordance with the specifica tions of the wall manufacturer and the required exchange parts as shown on Figure 13 Insert the ERK MB V into the prepared exchange part Average out the circumfer...

Страница 15: ...xamples of connection to smoke extraction duct Figure 16 Examples of connection to smoke extraction duct Please note The connection is made via bonding and sealing of the contact surfaces and with the...

Страница 16: ...extrac tion duct used incl bonding with waterglass based adhesive In the sleeve connection area the ERK MB housing must be hung independently of the smoke extraction duct pos 22 1 Housing of the ERK M...

Страница 17: ...f connection to smoke extraction duct Figure 20 Examples of connection to smoke extraction duct Please note The connection is made via bonding and sealing of the contact surfaces and with the help of...

Страница 18: ...the vertical smoke extraction duct 1 Housing of the ERK MB 21 Smoke extraction duct in accordance with EN 12101 7 tested according to EN 1366 8 22 ERK MB suspension 24 Coarse thread screw 3 9 45 dista...

Страница 19: ...4 0026 for suspension of the smoke extraction blade dampers M8 to M12 Figure 22 Suspension fastening M8 to M12 M16 and M20 Figure 23 Suspension fastenings M16 and M20 for M16 l for M20 l U weight 5 8...

Страница 20: ...in the approval notification the calculated tensile load per do wel must not exceed 500 N Special dowels with a maximum tensile load of 700 N can be also used Please note To design suspension with th...

Страница 21: ...uilt in sufficient numbers and size and must not im pair the functioning of the smoke extraction blade dampers they may lead to increasing the distances 1 The distance between smoke extraction blade d...

Страница 22: ...ise level LWA dB A Damper width B 200 mm Diagram 1 Design diagram B 200 mm Damper width B 300 mm Diagram 2 Design diagram B 300 mm Damper width B 400 mm Diagram 3 Design diagram B 400 mm Please note T...

Страница 23: ...l LWA dB A Damper width B 500 mm Diagram 4 Design diagram B 500 mm Damper width B 600 mm Diagram 5 Design diagram B 600 mm Damper width B 700 mm Diagram 6 Design diagram B 700 mm Please note The desig...

Страница 24: ...LWA dB A Damper width B 800 mm Diagram 7 Design diagram B 800 mm Damper width B 900 mm Diagram 8 Design diagram B 900 mm Damper width B 1000 mm Diagram 9 Design diagram B 1000 mm Please note The desi...

Страница 25: ...e loss p in Pa must be multiplied by the following as signed factors depending on the installation situation with constant The sound power level LWA in dB A is corrected using the cal culated pressure...

Страница 26: ...ST 24 V AC DC EK21 BE230 12 230 V AC o Communication devices for actuator EK12 EK14 e g SPMa1SR part of EK14 or SPLM 4S 0SD Mod on site o Profile connection frame type PAR for connecting among others...

Страница 27: ...VDE guidelines Technical data Table 8 Technical data of actuators Actuator type EK10 SEL 1 90 EK11 SEL 2 90 EK12 SEL 1 90 SLC EK14 EK12 SPMa 1SR Rated voltage V AC DC 24 AC 230 In connection with SPM...

Страница 28: ...SEL 1 90 24 V AC DC and EK11 SEL 2 90 230 V AC 2 point or 1 cable con trol 7 strand Picture showing OPEN 2 Blade dampers parallel 40 mm thick 4 Actuator 5 Housing of the actuator and transmission rod...

Страница 29: ...es loose Model galvanised sheet steel Recommendation mounting ex works Figure 28 Profile connection frame type PAR Flexible connection spigot type FS E The flexible spigot type FS E has a temperature...

Страница 30: ...F10 for reinforced concrete walls only 16 Profile UW 50 40 0 6 for wall thickness 100 mm for larger wall thicknesses the profiles must be adapted accordingly 17 Profile CW 50 50 0 6 for wall thicknes...

Страница 31: ...DC STANDARD ACTUATOR EK11 SEL 2 90 230 V AC EK12 SEL 1 90 SLC 24 V AC DC additional communication de vice required please order separately EK14 EK12 including additional required communication device...

Страница 32: ...ensi ons and connections o in and on the front and on the side of vertical smoke extraction ducts with additional on site suspensions and connections Product SCHAKO type ERK MB Declaration of Performa...

Страница 33: ...ch loose Product SCHAKO type FS E Dimensions Width W mm Height H mm Mounting bracket type WE S made of galvanised sheet steel dimensions 100 x 100 x 160 mm Required for installation on solid smoke ext...

Страница 34: ...nes for service according to DIN 31051 and EN 13306 For and after commissioning the function of the entire smoke extraction system interaction of all components must be regu larly checked and document...

Страница 35: ...damper no Declaration of perfor mance no Series Actuator The following functional steps have been carried out according to the documents installation mounting and operating instructions before commis...

Страница 36: ...fo schako de Web www schako de SAMPLE Functional test protocol for smoke extraction blade dampers Cons No ____________________ Defects found during the test on ________________________________________...

Страница 37: ...g L 2343 Luxembourg A 1060 Wien PL 05 500 Piaseczno Phone 352 403 157 1 Phone 352 403 157 1 Phone 43 1 890 24 62 Phone 48 22 7263570 Fax 352 403 157 66 Fax 352 403 157 66 Fax 43 1 890 24 62 50 Fax 48...

Страница 38: ...tig an vertikaler Entrauchungsleitung 17 Abbildung 20 Anbindungsbeispiele an Entrauchungsleitung 17 Abbildung 21 Anbindung seitlich an vertikaler Entrauchungsleitung 18 Abbildung 22 Abh ngungsbefestig...

Отзывы: